Grid Setting/F(W)
F(W)
Start freq F
Over frequency
50.20Hz
Start delay F
0.00s
Stop freq F 51.5Hz
Droop F 40%PE/Hz
Stop delay F
0.00s
Start freq F
Under frequency
49.80Hz
Start delay F
Stop freq F 49.80Hz
Droop F 40%PE/Hz
Stop delay F
0.00s
0.00s
Grid
Set4
F(W): It's used to adjust the output active power of inverter
according to the grid frequency.
Droop F: percentage of nominal power per Hz
For example, "Start freq F=50.2Hz, Stop freq F=51.5,
Droop F=40%PE/Hz" when the grid frequency reaches
51.2Hz, the inverter will decrease its active power at
Droop F of 40%. And then when grid system frequency
is less than 50.1Hz, the inverter will stop decreasing
output power.
For the detailed setup values, please follow the local
grid code.
- 43 -
Reconnection Time PF
60s
1.000
Grid Setting/Connect
Low frequency
Normal connect
48.00Hz
Low voltage
185.0V
High frequency 51.50Hz
Normal Ramp rate 10s
Reconnect Ramp rate 36s
High voltage
265.0V
Low frequency
Reconnect after trip
Low voltage
High frequency
51.30Hz
High voltage
263.0V
48.20Hz
187.0V
Grid
Set2
Over voltage U>(10 min. running mean)
Grid Setting/IP Protection
260.0V
Set3
Grid
--
HV1
265.0V
0.10s
--
HV2
265.0V
0.10s
HV3
--
LV1
185.0V
0.10s
--
LV2
185.0V
0.10s
185.0V
LV3
--
HF1
51.50Hz
0.10s
--
HF2
0.10s
HF3
--
LF1
48.00Hz
0.10s
--
LF2
0.10s
LF3
0.10s—Trip time.
LV1: Level 1 undervoltage protection point;
LV2: Level 2 undervoltage protection point;
LV3: Level 3 undervoltage protection point.
HV1: Level 1 overvoltage protection point;
HV2: Level 2 overvoltage protection point;
HV3: Level 3 overvoltage protection point.
HF1: Level 1 over frequency protection point;
HF2: Level 2 over frequency protection point;
HF3: Level 3 over frequency protection point.
LF1: Level 1 under frequency protection point;
LF2: Level 2 under frequency protection point;
LF3: Level 3 under frequency protection point.
265.0V
51.50Hz
51.50Hz
48.00Hz
48.00Hz
Normal connect: The allowed grid voltage/frequency
range when the inverter operates normally.
Normal Ramp rate: It is the startup power ramp.
Reconnect after trip: The allowed grid voltage
/frequency range for the inverter connects the grid
after the inverter trip from the grid.
Reconnect Ramp rate:It is the reconnection power ramp.
Reconnection time: The waiting time for the inverter
connects the grid again after tripping.
PF: Power factor, which is the ratio of active power to
apparent power in AC circuits and can be used to adjust
the output active power and reactive power of inverter.
215V
205V
240V
0%
240V
0%
235V
0%
235V
0%
258V
255V
244V
255V
220V
0%
230V
0%
220V
0%
220V
0%
rated
rated
rated
rated