Error code
F22
Tz_EmergStop_Fault
Remotely shutdown
It means the inverter is remotely controlled.
F23 Tz_GFCI_OC_Fault
Leakage current fault
1. Check PV side cable ground connection.
2. Restart the system 2~3 times.
F24 DC_Insulation_Fault
F26 BusUnbalance_Fault
PV isolation resistance is too low
1. Check the connection of PV panels and inverter is firm and
correct.
2. Check whether the PE cable of inverter is connected to
ground.
F25 DC_Feedback_Fault Restart the inverter 3 times and restore the factory settings.
F27 DC_Insulation_Fault Restart the inverter 3 times and restore the factory settings.
1. Please wait for a while and check whether it is normal.
2. When the load power of 3 phases has a big different, it will
report the F26.
3 .When there's DC leakage current, it will report F26.
4. Restart the system 2~3 times.
F28 DCIOver_M1_Fault Restart the inverter 3 times and restore the factory settings.
F29
Parallel_Comm_Fault
1. When inverters are connected in parallel, check the parallel
communication cable connection and hybrid inverter
communication address setting.
2. During the parallel system startup period, inverters will
report F29. But when all inverters are in ON status, it will
disappear automatically.
F30 AC_MainContactor_Fault
F31 AC_SlaveContactor_Fault
F32 DCIOver_M2_Fault
1. Check whether the grid orientation is correct,
2. Restart the inverter 3 times and restore the factory settings
Restart the inverter 3 times and restore the factory settings.
Restart the inverter 3 times and restore the factory settings.
F33 AC_OverCurr_Fault
1. Check whether the grid current is too large.
2. Restart the inverter 3 times and restore the factory settings.
F21 Tz_HV_Overcurr_Fault
BUS over current
1. Check the PV input current and battery current setting.
2. Restart the system 2~3 times.
F20 Tz_Dc_OverCurr_Fault
DC side over current fault
1. Check PV module connection and battery connection;
2. When in the off-grid mode, starting the inverter under a high
power load may report F20. Please reduce the load power
connected.
3. If it remains the same, turn off DC and AC switches for one
minute, then turn on the DC and AC switches.
Description Solutions
F34 AC_Overload_Fault
Check the backup load connection, make sure it is within the
allowed power range.