5.6 Battery Setting Menu
Batt Capacity: Reserved.
Use Batt V: Use battery voltage for all battery related
settings.
Max. A charge/discharge: Max battery charge/discharge
current(0-50A for 25kW model,0-75A for 29.9/30kW model ).
For AGM and Flooded, we recommend Ah battery
size x 20%= Charge/Discharge amps.
. For Lithium, we recommend Ah battery size x 50% =
Charge/Discharge amps.
. For Gel, follow manufacturer' s instructions.
No Batt: tick this item if no battery is connected to
the system.
Parallel bat1&bat2: This parameter is not available for
this model of inverter.
Gen Force: When the generator is connected, it is forced
to start the generator without meeting other conditions.
This is Battery Setup page.
Start =30%: Percent SOC below 30% system will AutoStart
a connected generator to charge the battery bank.
A = 20A: The maximum charging current that the
generator can support.
Gen Charge: Use the power of diesel generator to
charge the battery.
Gen Signal: The normally open relay will close when the
battery SOC or voltage drop to the set value of "Start".
①
Grid Charge
Gen Charge
Grid SignalGen Signal
Gen Max Run Time 24.0 hours
Gen Down Time 0.0 hours
Battery Setting
Start
A
30% 30%
20A
37A
Batt
Set2
Start =30%: When battery SOC or voltage
drop to this set value, inverter will start the
generator connected to the grid port
automatically to charge the battery.
A = 37A: maximum charging current when
only use the power fed from the grid port of
inverter as the power source, which means
using the power of grid or the power of
generator connected to the grid port.
Grid Charge: It's allowed to use power fed
from the grid port, which includes grid or
generator connected to the grid port, to
charge the battery.
Grid Signal: When a generator is connected
to the grid port of hybrid inverter, this 'Grid
signal' can be used to control the dry contact
to start or stop the generator.
This is Grid Charge, you need select.
①
②
②
③
③
Gen Max Run Time: It indicates the longest time
Generator can run in one day, when time is up, the
Generator will be turned off. 24H means that it does
not shut down all the time.
Gen Down Time: It indicates the rest time of the
Generator before the inverter start it again.
Batt Mode
Lithium
Use Batt V
Battery Setting
Parallel bat1&bat2
Gen Force
Max A Charge
Batt Capacity
Max A Discharge 0A
0A
0Ah
Batt
Mode
No Batt
Bekijk gratis de handleiding van Deye SUN-25K-SG02HP3-EU-AM3, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
Merk | Deye |
Model | SUN-25K-SG02HP3-EU-AM3 |
Categorie | Niet gecategoriseerd |
Taal | Nederlands |
Grootte | 7788 MB |