Master positive relay
adhesion
Relay feedback information state adhesion
Fuse Blown
No high voltage is detected after the loop relay is
closed
Repeated BMU
address fault
BMU with the same number
INTER-CAN BUS
communication failure
Loss of communication between BMS
PCS-CAN BUS
communication failure
The heartbeat message of the inverter is not
received for a long time
RS485 communication
failure
Inverter RS485 access is not received for a long time
Abnormal RS485
communication
C
External total voltage
acquisition fault
/
Internal total voltage
acquisition fault
The difference between the acquired internal total
voltage and the accumulated internal total voltage
exceeding the set value
SCHG total voltage
acquisition fault
/
Cell voltage
acquisition fault
The cell voltage acquired is 0
Temperature
acquisition failure
The temperature acquired is -40
Current acquisition
fault
/
Current module fault Abnormal Hall current/reference voltage
EEPROM storage
failure
EEPROM write failure during self-test
RTC clock fault
The external RTC failed to enable the charging
function
Pre-charge failure Pre-charge timeout
Charging voltage too
low
The minimum cell voltage is lower than the set value
BMU lost BMU message not received for a long time
Abnormal number of
BMU
The number of BMU addresses is different from the
number of set parameters