Maximum current 10 mA
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
Ground for reference and controls
Same as terminal #7
Digital inputs can be disconnected from ground (*)
Must be connected to GND or 24 V of I/O term.
or to ext.24 V or GND
Selection with jumper block X3 (*)
Ri = min. 5 kΩ
18-30 V = 1
Ri = min. 5 kΩ
18-30 V = 1
Output signal range: Current 0(4)-20 mA,
RL max 500 Ω or
Voltage 0-10 V, RL >1kΩ
Selection with jumper block X6 (*)
Maximum Uin = 48 VDC
Maximum current = 50 mA
Open collector output
AO1-
DO1
+24V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
CMA
CMB
Standard I/O board
Terminal Signal Description
+10V
ref
AI1+
GND/AI1-
AI2+
GND/AI2-
+24V
Reference voltage
Analogue input,
voltage or current
Analogue input,
voltage or current
24 V aux. voltage
I/O ground
Analogue input common
Analogue input common
Common A for DIN1—DIN3
Common B for DIN4-DIN6
Analogue signal (+output)
Analogue output common
Control voltage output
I/O ground
AO1+
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
Differential input if not connected to ground
Allows ±20 V common mode voltage to GND
Selection V/mA with jumper block X1 (*)
0...+10 V (Ri = 200 kΩ)
(-10V...+10V Joystick ctrl, sel. with jumper)
0-20 mA (Ri =250 Ω)
±15%, max. 250 mA (all boards total)
150 mA (from single board)
Can also be used as external power back-up for
the control unit (and fieldbus)
Same as terminal #6
Digital input 1
Digital input 4
Digital input 5
Digital input 6
Digital input 2
Digital input 3
Reference potentiometer,
1-10kΩ
Illustration 53: Control Terminal Signals on OPTA1
*)
See figure in 7.3.2.2 Jumper Selections on the OPTA1 Basic Board
Parameter references for I/O on control panel and NCDrive are: An.IN:A.1, An.IN:A.2, DigIN:A.1, DigIN:A.2, DigIN:A.3, DigIN:A.4, Dig-
IN:A.5, DigIN:A.6, AnOUT:A.1 and DigOUT:A.1.
To use the control voltage output +24 V/EXT+24 V:
Wire the +24 V control voltage to digital inputs through an external switch. OR
Use the control voltage to power up external equipment, such as encoders and auxiliary relays.
The specified total load on all available +24 V/EXT+24 V output terminals must not exceed 250 mA.
The maximum load on the +24 V/EXT+24 V output per board is 150 mA. If there is a +24 V/EXT+24 V output on the board, it is locally
short circuit protected. If one of the +24 V/ EXT+24 V outputs short circuits, the others remain powered because of the local protec-
tion.
AQ468246143802en-000201 / DPD00888 | 71Danfoss A/S © 2023.09
Control Unit
VACON® NXP IP00 Drive Modules
Operating Guide