Example 4
A1
U V
W
U
V
W
dUdt dUdt
PE
PE
A
B
C
1
2 2
2
4 4
1
1
3 3
5
5
5
e30bj124.10
Illustration 14: Example Installation 4
1
NFE units
2
AC chokes
3
FI13 (inverter unit)
4
dU/dt filter
5
DC busbars
Table 14: Cabinet Data for Installation Example 4
This installation applies to drive type:
NXP1500 6 (6-pulse)
Minimum required cabinet width:
800 mm (Cab. A) + 800 mm (Cab. B) + 800 mm (Cab. C)
(31.50 in (Cab. A) + 31.50 in (Cab. B) + 31.50 in (Cab. C))
Minimum required cabinet height:
2200 mm
(86.61 in)
Required weight carrying capacity:
635 kg (1399.9 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B); 540 kg (1190.5 lb) (Cab. C)
Protection rating:
This manual applies to IP21.
Construction:
According to EN60439-1
Ventilation openings:
See 5.2.1 Ventilation of the Cabinet.