Danfoss VACON NXP handleiding

178 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 35 van 178
Example 3
A1
A1
dUdt
A
B
C
1
2 2 2 2
1 1 1
3
4
U
V
W
PE
5
5
5
e30bj125.10
Illustration 13: Example Installation 3
1
NFE units
2
AC chokes
3
FI13 (inverter unit)
4
dU/dt filter
5
DC busbars
Table 13: Cabinet Data for Installation Example 3
This installation applies to drive types:
NXP1300 5 (12-pulse)
NXP1450 5 (12-pulse)
Minimum required cabinet width:
600 mm (Cab. A) + 800 mm (Cab. B) + 600 mm (Cab. C)
(23.62 in (Cab. A) + 31.50 in (Cab. B) + 23.62 in (Cab. C))
Minimum required cabinet height:
2200 mm
(86.61 in)
Required weight carrying capacity:
450 kg (992.08 lb) (Cab. A and C); 540 kg (1190.5 lb) (Cab. B)
Protection rating:
This manual applies to IP21.
Construction:
According to EN60439-1
Ventilation openings:
See 5.2.1 Ventilation of the Cabinet.
AQ468246143802en-000201 / DPD00888 | 35Danfoss A/S © 2023.09
Mounting the Unit
VACON® NXP IP00 Drive Modules
Operating Guide

Bekijk gratis de handleiding van Danfoss VACON NXP, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDanfoss
ModelVACON NXP
CategorieNiet gecategoriseerd
TaalNederlands
Grootte20640 MB