AQ304230922416en-000101 | IC.PS.P21.L1.02 | 5
2.2
6 wires output 18 AWG 1.65 mm OD
CONNECTIONS
White: +Vs (+10 - +36 Vdc)
Yellow: GROUND
Grey: CAN-H
Blue: CAN-L
Pink: NC
Green: NC
Brown: NC
Cables output IEC 60332
Cable 7 pole 0.5 mm²
OD 6.4 mm
NOTE:
Please make sure that the CANbus is terminated.
The impedance measured between CAN-H and
CAN-L must be 60 ohm that means the cable
must be connected to a 120 ohm resistor on each
ends of the bus line. Internally the tranducer is
not terminated with the resistor of 120 ohm.
Do not confuse the signal lines of the CAN bus,
otherwise communication with the transducer is
impossible.