Handleiding
Je bekijkt pagina 41 van 49

Some systems require additional charging depending on pipe lengths. The standard pipe length
varies according to local regulations. For example, in North America, the standard pipe length is
7.5m (25'). The refrigerant should be charged from the service port on the outdoor unit's low pres-
sure valve. The additional refrigerant to be charged can be calculated using the following formula:
NOTE ON ADDING REFRIGERANT
Liquid Side Diameter
Refrigerant Φ6.35(1/4”) Φ9.52(3/8”) Φ12.7(1/2”)
R401A:
(orifice tube in the indoor unit):
R401A:
(orifice tube in the outdoor unit):
(Total pipe length
-standard pipe length)
x30g(0.32oz)/m(ft)
(Total pipe length
-standard pipe length)
x15g(0.16oz)/m(ft)
(Total pipe length
-standard pipe length)
x65g(0.69oz)/m(ft)
(Total pipe length
-standard pipe length)
x115g(1.23oz)/m(ft)
(Total pipe length
-standard pipe length)
x65g(0.69oz)/m(ft)
(Total pipe length
-standard pipe length)
x30g(0.32oz)/m(ft)
CAUTION: DOT NOT MIX REFRIGERANT TYPES
Page 41
Bekijk gratis de handleiding van Daizuki DX1C18426-21, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daizuki |
| Model | DX1C18426-21 |
| Categorie | Airco |
| Taal | Nederlands |
| Grootte | 6253 MB |







