9 Technical data
Installation and operation manual
34
SERHQ020~032BAW1 + SEHVX20~64BAW
Split packaged air-cooled water chiller
4P508019-1D – 2019.11
9 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin Business Portal (authentication required).
9.1 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and
the minimum space for air inlet and air outlet is available (refer to the
figure below and choose one of the possibilities).
In case of an installation site where sides A+B+C+D have
obstacles, the wall heights of sides A+C have no impact on
service space dimensions. Refer to the figure for impact of wall
heights of sides B+D on service space dimensions.
In case of an installation site where only sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.
b
a c
d
A C
B
D
a e
b
d
e
A C
B
D
21
c
a ce
b
d
f
A C
B
D
3
a ce
b
b
d
A C
B
D
4
Layout A+B+C+D A+B
Possibility 1 Possibility 2
1 a≥10mm
b≥300mm
c≥10mm
d≥500mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
a≥200mm
b≥300mm
2 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
a≥200mm
b≥300mm
e≥400mm
3 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
f≥600 mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
f≥500mm
4 a≥10mm
b≥300mm
c≥10mm
d≥500mm
e≥20mm
a≥50mm
b≥100mm
c≥50mm
d≥500mm
e≥100mm
h
1
h
2
1500
500
ABCD Sides along the installation site with obstacles
F Front side
Suction side
INFORMATION
The service space dimensions in above figure are based
on cooling operation at 35°C ambient temperature
(standard conditions).
INFORMATION
Further specifications can be found in the technical
engineering data.
9.2 Service space: Indoor unit
Make sure the space around the unit is adequate for servicing (refer
to the figure below).
766.5 500200
396500
(mm)
CAUTION
Make sure the right service panel can still be removed after
installation of the piping.
INFORMATION
Further specifications can be found in the technical
engineering data.