6 Installation
Installer reference guide
19
RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L
Split system air conditioners
4P473074-1A – 2019.04
6.7.3 Precautions when connecting the
electrical wiring
INFORMATION
Also read the precautions and requirements in the
following chapters:
General safety precautions
Preparation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
For use of units in applications with temperature alarm
settings it is recommended to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.
6.7.4 Guidelines when connecting the electrical
wiring
Keep the following in mind:
If stranded conductor wires are used, install a round crimp-style
terminal on the end of the wire. Place the round crimp-style
terminal on the wire up to the covered part and fasten the terminal
with the appropriate tool.
b a
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
c b
c
aa
A
AA´
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor
wire with round
crimp-style terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
O Allowed
X NOT allowed
Tightening torques
Item Tightening torque (N•m)
M4 (X1M) 1.2~1.8
Item Tightening torque (N•m)
M4 (earth) 1.2~1.4
M5 (X1M) 2.0~3.0
M5 (earth) 2.4~2.9
6.7.5 Specifications of standard wiring
components
Component V1 Y1
71 71 100 125+140
Power supply
cable
MCA
(a)
20.6A 14.0A 21.0A 22.5A
Voltage 230V 400V
Phase 1~ 3N~
Frequency 50Hz
Wire sizes Must comply with applicable
legislation
Interconnection cables Minimum cable section of 2.5
mm² and applicable for 230 V
Recommended field fuse 25A 16A 25A
Earth leakage circuit breaker Must comply with applicable
legislation
(a) MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
6.7.6 To connect the electrical wiring on the
outdoor unit
NOTICE
Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "6.2.2 To open the outdoor
unit"on page10.
2 Strip insulation (20mm) from the wires.
a b
a Strip wire end to this point
b Excessive strip length may cause electrical shock or
leakage.
3 Connect the interconnection cable and power supply as follows:
c
a
d
e
1~50 Hz
220-240 V
3N~50 Hz
380-415 V
V1 Y1
L1 L2 L3
L1 L2 L3
N
b
b
a Interconnection cable
b Power supply cable
c Earth leakage circuit breaker
d Fuse
e User interface