Daikin RZQG125L8Y1L handleiding

32 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 18 van 32
6 Installation
Installer reference guide
18
RZQG71L9V1L + RZQG71~125L8Y1L + RZQG140L7Y1L
Split system air conditioners
4P473074-1A – 2019.04
To determine the additional refrigerant amount (R in kg)
L1 (m)
L1 (standard): 30~40m 40~50m 50~60m
(a)
60~75m
(a)
L1 (size-up): 15~20m 20~25m 25~30m
(a)
30~35m
(a)
R: 0.5kg 1.0kg 1.5kg 2.0kg
(a) Only for RZQG100~140.
6.6.4 To determine the complete recharge
amount
When piping length is <5 m, a complete recharge of the unit is
required.
To determine the complete recharge amount (kg) (in case of
standard liquid pipe size)
Model
L1 (m)
3~10 10~20 20~30 30~40 40~50 50~60 60~75
RZQG71 1.9 2.4 2.9 3.4 3.9
RZQG100~140 3.0 3.5 4.0 4.5 5.0 5.5 6.0
To determine the complete recharge amount (kg) (in case of
size‑up liquid pipe size)
Model
L1 (m)
3~5 5~10 10~15 15~20 20~25 25~30 30~35
RZQG71 1.9 2.4 2.9 3.4 3.9
RZQG100~140 3.0 3.5 4.0 4.5 5.0 5.5 6.0
To determine the complete recharge amount (kg) (in case of
size‑down liquid pipe size)
Model
L1 (m)
3~10
RZQG71 1.9
RZQG100~140 3.0
6.6.5 Charging refrigerant: Setup
See "6.5.3Checking refrigerant piping: Setup"on page16.
6.6.6 To charge additional refrigerant
WARNING
Only use R410A as refrigerant. Other substances may
cause explosions and accidents.
R410A contains fluorinated greenhouse gases. Its
global warming potential (GWP) value is 2087.5. Do
NOT vent these gases into the atmosphere.
When charging refrigerant, always use protective
gloves and safety glasses.
CAUTION
To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
Prerequisite: Before charging refrigerant, make sure the refrigerant
piping is connected and checked (leak test and vacuum drying).
1 Connect the refrigerant cylinder to both the service port of the
gas stop valve and the service port of the liquid stop valve.
2 Charge the additional refrigerant amount.
3 Open the stop valves.
If pump down is needed in case of dismantling or relocating the
system, see To pump down for more details.
6.6.7 To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b Factory refrigerant charge: see unit name plate
c Additional refrigerant amount charged
d Total refrigerant charge
e Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
2
equivalent.
f GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label. That GWP is based on the current legislation on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2 Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
6.7 Connecting the electrical wiring
6.7.1 About connecting the electrical wiring
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1 Making sure the power supply system complies with the
electrical specifications of the units.
2 Connecting the electrical wiring to the outdoor unit.
3 Connecting the electrical wiring to the indoor units.
4 Connecting the main power supply.
6.7.2 About electrical compliance
RZQG71_V1 + RZQG100~140_Y1
Equipment complying with:
EN/IEC 61000‑3‑12 provided that the short-circuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
point between the user's supply and the public system.
EN/IEC 61000‑3‑12 = European/International Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16A and ≤75A per phase.
It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to the
minimum S
sc
value.
Model Minimum S
sc
value
RZQG71_V1 + RZQG100~140_Y1 1170kVA

Bekijk gratis de handleiding van Daikin RZQG125L8Y1L, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelRZQG125L8Y1L
CategorieAirco
TaalNederlands
Grootte5226 MB