11 | Commissioning
Installer reference guide
71
RZASG100~140MUV/Y
Sky Air Advance-series
4P743506-1 – 2023.08
Error code Possible cause
E7 There is a missing phase in case of three-phase
power supply units.
Note: Operation will be impossible. Turn OFF the
power, recheck the wiring, and switch two of the
three electrical wires.
L4 The air inlet or air outlet is blocked.
U0 The stop valves are closed.
U2 There is a voltage imbalance.
There is a missing phase in case of three-phase
power supply units. Note: Operation will be
impossible. Turn OFF the power, recheck the
wiring, and switch two of the three electrical
wires.
U4 or UF The inter-unit branch wiring is not correct.
UA The outdoor and indoor unit are incompatible.
NOTICE
The reversed phase protection detector of this product only functions when the
product starts up. Consequently reversed phase detection is not performed
during normal operation of the product.
The reversed phase protection detector is designed to stop the product in the
event of an abnormality when the product is started up.
Replace 2 of the 3 phases (L1, L2, and L3) during reverse-phase protection
abnormality.