11 | Commissioning
Installer reference guide
70
RZASG100~140MUV/Y
Sky Air Advance-series
4P743506-1 – 2023.08
# Action Result
1 Press.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Position 0
Low
2 Select Position 0.
Return Setting
Return Setting
Air Volume/direction
Air Volume Direction
Low
Position 0
3 Change the position. If the airflow flap of the indoor
unit moves, operation is OK.
If not, operation is not OK.
4 Press. The home menu is displayed.
5 Stop the test run.
# Action Result
1 Press at least 4seconds. The Service Settings menu is
displayed.
2 Select Test Operation.
Return Setting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
3 Press. The unit returns to normal
operation, and the home menu
is displayed.
11.5 Error codes when performing a test run
If the installation of the outdoor unit has NOT been done correctly, the following
error codes may be displayed on the user interface:
Error code Possible cause
Nothing displayed
(the currently set
temperature is not
displayed)
The wiring is disconnected or there is a wiring
error (between power supply and outdoor unit,
between outdoor unit and indoor units, between
indoor unit and user interface).
The fuse on the outdoor unit PCB has blown out.
E3, E4 or L8 The stop valves are closed.
The air inlet or air outlet is blocked.