17 Electrical installation
Installation and operation manual
39
RXYSA8~12AMY1B
VRV 5-S system air conditioner
4P752781-1C – 2024.10
Wire type Installation method
Stranded conductor
wire with round crimp-
style terminal
c b ba c
a
B
B
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
For earth connections, use the following method:
Wire type Installation method
Single-core wire
Or
Stranded conductor
wire twisted to "solid-
like" connection
d
a
b c
f
e
a Clockwise curled wire (single-core or
twisted stranded conductor wire)
b Screw
c Spring washer
d Flat washer
e Coupling washer
f Sheet metal
Tightening torques
Wiring Screw size Tightening torque
Transmission wiring M3.5 0.8~0.97N•m
Power supply wiring 8HP: M5 2.2~2.7N•m
10+12HP: M8 5.5~7.3N•m
17.4 To connect the electrical wiring to
the outdoor unit
CAUTION
▪ When connecting the power supply: connect the earth
cable first, before making the current-carrying
connections.
▪ When disconnecting the power supply: disconnect the
current-carrying cables first, before separating the earth
connection.
▪ The length of the conductors between the power supply
stress relief and the terminal block itself MUST be as
such that the current-carrying wires are tautened before
the earth wire is in case the power supply is pulled
loose from the stress relief.
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1 Remove the service cover. See "14.2.1 To open the outdoor
unit"[428].
2 Connect the transmission wiring as follows:
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
a
a
b
b
8 HP 10+12 HP
X1M (A1P)
F1 F2 SFB
a
a a a
a a
a
X3M
F1 Q2F2F1 Q1F2
TO MULTI
UNIT
TO OUT/DTO IN/D
a Use the conductor of sheathed wire (2wire) (no polarity)
b Terminal board (field supply)
Note: The indoor F1/F2 interconnection cable MUST be shielded:
▪ 8 HP: the shielding is earthed (only at outdoor unit side of the
cable) via the middle screw on the terminal X3M.
▪ 10+12HP: the shielding is earthed (only at outdoor unit side of the
cable) via a metal P-clamp. Strip the insulation up to the shielding
mesh, to provide full contact of the earth with the shielding. See
illustration below:
a
a P-clamp for cable shield earthing
Note: For 10+12HP, the interconnection cable MUST pass through
the ferrite core 3times (3passes, 2turns). See illustration below:
3×
b
a
a Interconnection cable
b Ferrite core
3 Connect the power supply as follows:
3N~ 50
/
60
Hz
380-415
/
400
V
L1 L2 L3
L1 L2 L3
N
X1M
a
b
c
a Earth leakage circuit breaker
b Fuse
c Power supply cable
4 Fix the cables (power supply and interconnection cable) with a
cable tie to the stop valve attachment plate and route the wiring
according to the illustration below.