Daikin RXYA14A7Y1B handleiding
Handleiding
Je bekijkt pagina 27 van 64

14 Unit installation
Installation and operation manual
27
RYMA5+RXYA8~20A7Y1B
VRV 5 heat pump
4P739915-1C – 2024.10
DANGER: RISK OF BURNING/SCALDING
14×14×
5~12 HP 14~20 HP
Once the front plates open, the switch box can be accessed. See
"14.2.2To open the switch box of the outdoor unit"[427].
For service purposes, the pushbuttons on the main PCB need to be
accessed. To access these pushbuttons, the switch box cover does
not need to be opened. See "18.1.3 To access the field setting
components"[444].
14.2.2 To open the switch box of the outdoor
unit
NOTICE
Do NOT apply excessive force when opening the switch
box cover. Excessive force can deform the cover, resulting
in entering of water to cause equipment failure.
5~12 HP
2×
SW8
14~20 HP
6×
SW8
NOTICE
When closing the switch box cover, make sure that the
sealing material on the lower back side of the cover is NOT
caught and bent towards the inside (see figure below).
a
b
c
d
e
a Switch box cover
b Front side
c Power supply terminal block
d Sealing material
e Moisture and dirt could enter
NOT allowed
Allowed
14.3 Mounting the outdoor unit
14.3.1 To provide the installation structure
Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise.
NOTICE
▪ When the installation height of the unit needs to be
increased, do NOT use stands to only support the
corners.
▪ Stands under the unit must be at least 100mm wide.
NOTICE
The height of the foundation must at least be 150mm from
the floor. In heavy snowfall areas, this height should be
increased up to the average expected snow level,
depending on the installation place and condition.
≥100 mm
≥100 mm
*
NOT allowed
Allowed (* = preferred installation)
▪ The preferred installation is on a solid longitudinal foundation
(steel beam frame or concrete). The foundation must be larger
than the grey marked area.
729
≤613
≥929
≥AB
AA
a
(mm)
Minimum foundation
a Anchor point (4×)
HP AA AB
5~12 766 992
14~20 1076 1302
▪ Fasten the unit in place using four foundation bolts M12. It is best
to screw in the foundation bolts until their length remains 20 mm
above the foundation surface.
20 mm