8 Troubleshooting
Operation manual
23
LMCEY1A/W + LMCEY2A/W
Daikin LMC
4P753996-1 – 2024.06
Display
code
Description Trigger Effect Reset Troubleshooting
cht
High condensing
temperature warning.
Condenser may be
obstructed, causing a
higher temperature.
Unit continues
operation.
Automatic ▪ Check if the condenser is properly
cleaned from dust and dirt.
▪ Check if the air inlet and outlet of the
unit are obstructed, causing a
reduction of airflow to the condenser.
▪ Check that the water circuit is not
clogged (only for
LMCEY1W+LMCEY2W).
▪ Check that the plate heat exchanger
is fed with the prescribed water mass
flow (only for
LMCEY1W+LMCEY2W),.see
"5.1Operation range"[417].
▪ Check if the unit is working within the
temperature range prescribed into the
manual. See "5.1 Operation
range"[417].
▪ If the problem persists contact your
dealer/installer.
dor
Door open. Door has been opened
and the door switch is
active.
Unit operation stops. Automatic when
door is closed.
▪ Close the cold room's door.
▪ If the warning persists when the door
is closed, check if in this condition
microswitch is correctly actuated.
▪ If the problem persists Contact your
dealer/installer.
E1
Th3 suction air prove
error.
Th3 faulty or
disconnected.
Unit continues
operation with backup
Th5 thermistor control,
with +10°C offset.
Automatic ▪ Contact your dealer/installer.
E2
Th5 Eva inlet prove
error.
Th5 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
E3
Th6 Eva outlet prove
error.
Th6 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
E4
Th1 Discharge prove
error.
Th1 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
E6
Th7 Discharge prove
error.
Th7 faulty or
disconnected.
Unit stops operation
except the evaporator
fan.
Automatic ▪ Contact your dealer/installer.
Ed1
Defrost terminated
after maximum time.
Defrost on evaporator
1 ended by defrost
timeout dP1.
Defrost ends, nomral
operation starts.
Defrost ends and
unit continues
operation.
▪ Check if the evaporator is properly
cleaned from ice or dirt.
▪ Avoid to Open the cold room door for
a minimum of 4 hours to avoid
moisture and ice, and allow the unit to
perform another defrost.
▪ If the problem persists contact your
dealer/installer.
Etc Real time clock error
(not set or not
updated).
Real time clock not
updated.
Unit continues
operation but timer
operations like the
scheduler will not
work.
Automatic ▪ Set Real Time Clock from Daikin
Apps: Setting/Device/Set data/time.
▪ If the problem persist contact your
dealer/installer.