5 Operation
Operation manual
17
LMCEY1A/W + LMCEY2A/W
Daikin LMC
4P753996-1 – 2024.06
b Periodically logged variables
c
Legend
The log view is pre-set, however it CAN be changed using the
legend choice. In addition, the pre-set views loaded on the device
allow the main values to be filtered (temperature, HACCP alarms,
blackouts, etc.). To download the logs, use the drop-down menu at
the top right.
The periodic logs record the main values at regular intervals, as
shown in the table below.
Logged value
UOM Period
Control temperature
°C/°F 5min
Current temperature set point.
°C/°F 1h
Maximum temperature in the period
°C/°F 1h
Minimum temperature in the period
°C/°F 1h
Current evaporation temperature
°C/°F 1h
Current condensing temperature
°C/°F 1h
Compressor, minutes ON in the
period
min 1h
Compressor, starts in the period
- 1h
Evaporator fan, minutes ON in the
period
min 1h
Event logs are recorded when specific conditions occur, and can be
used to store certain related values, as shown in the table below.
The type of alarm recorded in the log can be identified using the
alarm information (see "8.1Error codes: Overview"[422]).
Logged
value
Event Other recorded
values
Sample
s*
Limit
s
Alarm
Alarm
activation
Number of the active
alarm with highest
priority.
Alarm status (active/
ceased)
20 max
255
alarm
Blackout
Device ON Power failure duration
in minutes
20 1000
hours
HACCP
alarms
HA or HF
alarm
Type HA or HF alarm 10 -
* The samples are stored in a circular FIFO list (e.g. for the alarms,
the 21st alarm overwrites the first alarm, and so on).
NOTICE
Changing the time set on the controller by more than
140minutes will clear the stored logs.
The alarm log can be deleted using the Daikin Apps (Bluetooth
connection only) using the specific command on the alarms page.
INFORMATION
Deleting the alarm log is irreversible.
For the alarm list with the codes and descriptions, see "8.1 Error
codes: Overview"[422].
5
Operation
5.1
Operation range
For air cooled units
Temperature type
Temperature range
Ambient temperature
+5~+45°C
Temperature type
Temperature range
Cooling temperature
Low temperature
setting (freezer)
From –25°C
Medium temperature
setting (cooler)
Up to +10°C
50
45
40
35
30
25
20
15
10
5
0
0 10 20 30 35 40 45 50-10-30 -20
-25
Tc [°C]
Ta [°C DB]
b
a
c
d
a Ambient temperature (Ta)
b
Operation range
c
Pull-down area
d
Cold room temperature (Tc)
For water cooled units
Temperature type
Temperature range
Ambient temperature
+5~+45°C
Water temperature
+5~+48°C
Cooling temperature
Low temperature
setting (freezer)
From –25°C
Medium temperature
setting (cooler)
Up to +10°C
50
45
40
35
30
25
20
15
10
5
0
0 10 20 30 35 40 45 50-10-30 -20
-25
Tc [°C]
Ta [°C DB]
b
a
c
d
48
45
40
35
30
25
20
15
10
5
0
0 10 20 30 35 40 45 50-10-30 -20
-25
Tc [°C]
Tw [°C]
b
e
c
d