VRV IV System indoor unit
4P405267-1C – 2021.04
Installation and operation manual
23
A Option setup
00 Not applicable. Do not change the default value.
0 — — —
01 Not applicable. Do not change the default value.
0 — — —
02 Pump target ΔT (heating).
5 3~8 1 —
03 Allowable overshoot on leaving water.
3 1~5 0.5 °C
04 Not applicable. Do not change the default value.
0 — — —
b Settings are not applicable
00 Not applicable. Do not change the default value.
35 — — —
01 Not applicable. Do not change the default value.
45 — — —
02 Not applicable. Do not change the default value.
1 — — —
03 Not applicable. Do not change the default value.
70 — — —
04 Not applicable. Do not change the default value.
70 — — —
C Leaving water temperature limits
00 Set point: heating leaving water maximum
temperature.
45 37~45 1 °C
01 Set point: heating leaving water minimum
temperature.
25 25~37 1 °C
02 Set point: cooling leaving water maximum
temperature.
20 18~22 1 °C
03 Set point: cooling leaving water minimum
temperature.
10 5~18 1 °C
04 Not applicable. Do not change the default value.
0 — — —
d Settings are not applicable
00 Not applicable. Do not change the default value.
10 — — —
01 Not applicable. Do not change the default value.
30 — — —
02 Not applicable. Do not change the default value.
15 — — —
03 Not applicable. Do not change the default value.
15 — — —
04 Not applicable. Do not change the default value.
40 — — —
E Service mode
00 Not applicable. Do not change the default value.
0 — — —
01 Not applicable. Do not change the default value.
0 — — —
02 Not applicable. Do not change the default value.
0 — — —
03 Not applicable. Do not change the default value.
1 — — —
04 Pump only operation.
0 0~25 1 —
F Settings are not applicable
00 Pump target ΔT (cooling).
5 3~8 1 —
01 Not applicable. Do not change the default value.
0 — — —
02 Not applicable. Do not change the default value.
1 — — —
03 Not applicable. Do not change the default value.
10 — — —
04 Not applicable. Do not change the default value.
50 — — —
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value