Installation and operation manual
22
HXY080+125A8V1BF
VRV IV System indoor unit
4P405267-1C 2021.04
8.4. Field setting list for Installation Manual
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level.
2 2~3 1
01 Room temperature compensation value.
0 –5~5 0.5 °C
02 Not applicable. Do not change the default value.
1
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0.
1 (ON) 0/1
1 Settings are not applicable
00 Not applicable. Do not change the default value.
1
01 Not applicable. Do not change the default value.
1:00
02 Not applicable. Do not change the default value.
0
03 Not applicable. Do not change the default value.
15:00
2 Automatic setback function
00 Status: setback operation.
1 (ON) 0/1
01 Setback operation start time.
23:00 0:00~23:00 1:00 hour
02 Setback operation stop time.
5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A).
–10 –20~5 1 °C
01 High ambient temperature (Hi_A).
15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti).
40 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti).
25 25~80 1 °C
4 Settings are not applicable
00 Not applicable. Do not change the default value.
1
01 Not applicable. Do not change the default value.
Fri
02 Not applicable. Do not change the default value.
23:00
5 Automatic setback and disinfection set point
00 Not applicable. Do not change the default value.
70
01 Not applicable. Do not change the default value.
10
02 Leaving water setback temperature.
5 0~10 1 °C
03 Room setback temperature.
18 17~23 1 °C
04 Not applicable. Do not change the default value.
0
6 Option setup
01 External room thermostat installed.
0 (OFF) 0/2
02 Heater kit option.
0 (OFF) 0/1
03 Not applicable. Do not change the default value.
0
8 Option setup
00 User interface temperature control.
0 (OFF) 0/1
01 Not applicable. Do not change the default value.
1
02 Emergency operation.
0 0/1
03 Not applicable. Do not change the default value.
1
04 Status: freeze-up prevention.
0 0~2 1
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating).
0 –2~2 0.2 °C
01 Leaving water thermistor auto corrective function.
1 (ON) 0/1 1
02 Not applicable. Do not change the default value.
0
03 Leaving water temperature compensation value
(cooling).
0 –2~2 0.2 °C
04 Not applicable. Do not change the default value.
0