19 | Commissioning
Installer and user reference guide
72
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
19.3 Checklist before commissioning
1 After the installation of the unit, check the items listed below.
2 Close the unit.
3 Power up the unit.
You have read the complete installation and operation instructions described in the
installer and user reference guide.
Installation
Check that the unit is properly installed, to avoid abnormal noises and vibrations when
starting up the unit.
Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
Ducting
Make sure the ducting is properly installed and insulated.
Field wiring
Check that the field wiring has been carried out according to the instructions described in
the chapter "18 Electrical installation" [4 65], according to the wiring diagrams and
according to the applicable national wiring regulation.
Power supply voltage
Check the power supply voltage on the local supply panel. The voltage MUST correspond to
the voltage on the nameplate of the unit.
Earth wiring
Be sure that the earth wires have been connected properly and that the earth terminals are
tightened.
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally installed protection devices are of the
size and type specified in the chapter "18Electrical installation"[465]. Be sure that no fuse
or protection device is bypassed.
Internal wiring
Visually check the switch box and the inside of the unit for loose connections or damaged
electrical components.
Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that the insulation work is properly
executed.
Damaged equipment
Check the inside of the unit for damaged components or squeezed pipes.
Field settings
Make sure all field settings you want are set. See "20.1Field setting"[474].
19.4 To perform a test run
INFORMATION
▪ Perform the test run according to the instructions in the outdoor unit manual.
▪ The test run is only completed if there is no malfunction code displayed on the
user interface or the outdoor unit 7‑segment display.
▪ See the service manual for the complete list of error codes and a detailed
troubleshooting guideline for each error.