16 | Unit installation
Installer and user reference guide
50
FXNA-A
VRV system air conditioner
4P785124-1 – 2024.09
Unit installed with the duct (side view)
c
a
b
OR
Ensure the discharge grille/duct airflow
is blowing in a horizontal or downward
direction (airflow direction MUST be
within the “allowed area” b). Install
appropriate measures (e.g. discharge
blades c) that will ensure the allowed
direction of airflow.
a Restricted area for airflow direction
b Allowed area for airflow direction
c Discharge blades (field supply)
▪ Use suspension bolts for installation.
▪ Mind the following requirements:
a
a
1750
A B
≥20
A Wall-mounted type
B Floor-standing type
a Minimum clearance
Top view:
≥300 ≥300
≥1000
(mm)
≥20
a
a Indoor unit
▪ Install the unit with a prebuilt fully enclosed casing with removable access panel,
suction air grille and discharge grille. These removable parts shall prevent access
to the unit and can ONLY be removed using a removal tool.
▪ In case of installation under a window sill, make sure that there is no short-circuit
of air.
16.2 Mounting the indoor unit
16.2.1 Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment, also read the installation
manual of the optional equipment. Depending on the field conditions, it might be
easier to install the optional equipment first.
▪ External static pressure. Refer to technical documentation to ensure that the
unit's external static pressure is not exceeded.