Daikin EWYQ050CAWH handleiding
Handleiding
Je bekijkt pagina 33 van 56

12 Technical data
Installer and user reference guide
33
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
12.3 Piping diagram: Outdoor module
Piping diagram: Outdoor module
M
INV
SV
HPS
STD1
HPS
STD2
HPS
SENPH
SENPL
SV
a c
d
q
e hdb fi g
d
v
m
j
d d d d
o o o
c
r
t
u
w
c
l
k
c
n p p p
d dd
q
q
x
sq
4TW27245-1
4TW27255-1
4TW27275-1
a Electronic expansion valve, subcooling (Y2E)
b Electronic expansion valve, main (Y1E)
c Check valve
d Filter
e Fan
f Fan motor (M1F, M2F)
g Heat exchanger
h Distributor
i Pressure regulating valve
j Accumulator
k 4-way valve, heat exchanger (Y3S)
l Solenoid valve, main (Y1S)
m High pressure sensor (SENPH)
n Solenoid valve (Y2S)
o Oil separator
p High pressure switch
q Capillary tube
r Compressor (INV)
s Compressor (STD1)
t Compressor (STD2)
u Low pressure sensor (SENPL)
v Service port, refrigerant charge
w Stop valve, liquid pipe
x Stop valve, gas pipe
Piping diagram: Hydro module
d+f
d+e c i
m
p n
l
o
m j a
b
b
b
b
R11T R14T
R12T R13T
A B
C
EWAQ*P*, EWYQ*P*,
EWAQ*H*, EWYQ*H*
EWAQ*N*,
EWYQ*N*,
h
gk g
D
E
a Air purge valve
b Temperature sensors (R11T, R12T, R13T, R14T)
c Expansion vessel (12 l)
d Shut-off valve (field installed)
e Water inlet connection
f Water outlet connection
g Drain port
h Water filter
i Pressure gauge
j Flow switch
k Pump
l Safety valve
m Check valve
n Electronic expansion valve
o Heat exchanger
p Filter
A Water side
B Refrigerant side
C Only for models with a pump
D Refrigerant flow in cooling mode
E Refrigerant flow in heating mode