12 Technical data
Installer and user reference guide
32
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
12 Technical data
A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is
available on the Daikin extranet (authentication required).
12.1 Overview: Technical data
This chapter contains information about:
Service space
Piping diagram
Wiring diagram
Field settings
ESP curves
12.2 Service space: Outdoor unit
Make sure the space around the unit is adequate for servicing and
the minimum space for air inlet and air outlet is available (refer to the
figure below and choose one of the possibilities).
a
d
c b
A+B+C+D
Possibility 1 Possibility 2
a≥300mm
b≥100mm
c≥500mm
d≥500mm
a≥500mm
b≥500mm
c≥500mm
d≥500mm
h
1
h
2
1500
500
F
(mm)
ABCD Sides along the installation site with obstacles
F Front side
Suction side
If the location of the installation is in a cold climate, then
dimensions a and b above should be >500 mm to avoid
accumulation of ice in between the outdoor units.
INFORMATION
Further specifications can be found in the technical
engineering data.