6 Installation
Installer and user reference guide
14
EWAQ016~064CAW + EWYQ016~064CAW
Packaged air-cooled water chiller
4P497339-1 – 2017.07
INFORMATION
Multi units are standard combinations.
Model Recommended fuses
EWAQ/EWYQ016 25A
EWAQ/EWYQ021 32A
EWAQ/EWYQ025 32A
EWAQ/EWYQ032 40A
EWAQ/EWYQ040 50A
EWAQ/EWYQ050 63A
EWAQ/EWYQ064 80A
NOTICE
When using residual current operated circuit breakers, be
sure to use a high-speed type 300 mA rated residual
operating current.
6 Installation
6.1 Overview: Installation
This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
▪ Mounting the outdoor unit
▪ Connecting the water piping
▪ Connecting the electrical wiring
6.2 Opening the units
6.2.1 To open the outdoor unit
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
To gain access to the unit, front plates need to be opened as follows:
1
3
2
4
5
4
5
Panel
1 Electrical parts of the hydro module
2 Hydro module (side panel)
3 Hydro module (front panel)
Panel
4 Outdoor module (left panel)
5 Outdoor module (right panel)
Once the front plates open, the electrical component box can be
accessed. See "6.2.2 To open the electrical component box of the
outdoor unit"on page14.
For service purposes, the pushbuttons on the main PCB need to be
accessed. To access these pushbuttons, the electrical component
box cover does not need to be opened. See "7.2.3 To access the
field setting components"on page21.
6.2.2 To open the electrical component box of
the outdoor unit
NOTICE
Do NOT apply excessive force when opening the
electronic component box cover. Excessive force can
deform the cover, resulting in entering of water to cause
equipment failure.
6.3 Mounting the outdoor unit
6.3.1 About mounting the outdoor unit
When
You have to mount the outdoor unit before you can connect the
water piping.
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the outdoor unit.
3 Providing drainage.
4 Protecting the unit against snow and wind by installing a snow
cover and baffle plates. See "Preparing installation site" in
"5Preparation"on page9.
6.3.2 To provide the installation structure
Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise.
NOTICE
When the installation height of the unit needs to be
increased, do NOT use stands to only support the corners.