5. INTRODUCTION
5.1. About the small inverter chiller
The unit is designed for outdoor installation (cooling: –15°C to 43°C,
heating: –15°C to 35°C) and can be combined with Daikin fan coil
units for air conditioning purposes. They can also be used for
supplying water for process cooling applications.
The units are available in 7 standard sizes with nominal capacities
ranging from 16.8 to 63 kW. All sizes are available as cooling only
unit (EWAQ) and as heat pump unit (EWYQ: cooling/heating).
The following tables show the technical and electrical specifications:
Technical specifications
Electrical specifications
The main components are
the compressor,
the air heat exchanger,
the water heat exchanger.
The compressor circulates refrigerant into the heat exchangers.
- In cooling mode, the refrigerant transports the heat taken
from the water heat exchanger to the air heat exchanger
where the heat is released to the air.
- In heating mode, the refrigerant transports the heat taken
from the air heat exchanger to the water heat exchanger
where the heat is released to the water.
5.2. Scope of this manual and how to get this manual
This document is an installation manual. It is intended for the installer
of this product. It describes the procedures for installing,
commissioning and maintaining the unit, and it will provide help if
problems occur. Carefully read the relevant parts of the manual.
This document is also an operation manual. It is intended for the
installer and the user of this product. It describes how to operate and
maintain the unit, and it will provide help if problems occur. Carefully
read the relevant parts of the manual.
A printed version of the manual is delivered with the unit.
Contact your local dealer for an electronic version of the manual.
For detailed instructions about how to install and operate the
associated products and/or optional equipment, refer to the relevant
catalogues, technical literature or product manuals for those
products.
EW A Q 016 BA W P —H—
EW Chiller
A A = Air to water cooling only model
Y = Air to water heat pump model
Q Refrigerant R410A
016 Indication of cooling capacity (kW)
For exact values, refer to the tables below
BA Series
W Voltage: 3P, 400 V
P P/H = Complete hydraulic package
N = Basic hydraulic package
—H— Depend on option
EWAQ/EWYQ
016 021 025 032 040 050 064
Dimensions
(HxWxD) (mm)
1684x
1371x
774
1684x
1684x
774
1684x
2358x
780
1684x
2980x
780
Unit weight (kg)
(a)
(a) For units with options OPSP or OPHP installed, the weight is slightly different.
Refer to the Engineering Databook for the exact values.
264 317 397 571 730
Connections G 1-1/4" female G 2" female
Expansion vessel
volume (l)
12 l
Plate heat
exchanger
water volume (l)
1.9 l 2.9 l 3.81 l 5.7 l
Internal piping
water volume (l)
3.2 l 4.2 l 5.8 l 7.7 l
Water circuit safety
valve (bar)
3 bar
External static
pressure (ESP)
• EWA/YQ*BAWP See figure 14
(b)
(b) External static pressure=External static pressure
Water flow=Water flow
• EWA/YQ*BAWH See figure 15
(b)
Pressure drop
EWA/YQ*BAWN
See figure 16
(c)
(c) Pressure drop=Pressure drop
Water flow=Water flow
Operation range
• cooling mode EWAQ/EWYQ See figure 17
(d)
(d) T
A
=Ambient temperature °C DB (dry bulb)
LWE=Leaving water evaporator temperature
LWC=Leaving water condenser temperature
EWC=Entering water condenser temperature
A=Optional water + glycol operation range
B=Standard water operation range
C=Pull down area
D=Pull up area
E=Protect the system against freezing by installing an optional water piping
heater tape or by filling up the system with a glycol solution.
• heating mode EWYQ See figure 18
(d)
Sound pressure
level (dBA)
(e)
(e) Sound pressure level is exclusive of the pump noise.
58 58 60 60 61 63 63
EWAQ/EWYQ
016 021 025 032 040 050 064
Phase 3N~
Frequency 50 Hz
Voltage 400 V (±10%)
Maximum running
current
for details see technical data book
Maximum starting
current
for details see technical data book
Recommended
fuses
for details see technical data book
4PWEN70082-1E_2016_12.book Page 3 Wednesday, December 7, 2016 2:18 PM