Installation and operation manual
41
EWAQ016~064BAW + EWYQ016~064BAW
Packaged air-cooled water chiller
4PW70082-1E – 2016.12
6.1.1. Field settings on the remote controller
First
code
Second
code
Setting name
Installer setting at variance
with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level
22~31—
01 Room temperature compensation value
0 –5~5 0.5 °C
02 Not applicable. Do not change the default value.
1—————
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1 — — —
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1 — — —
1 Settings are not applicable
00 Not applicable. Do not change the default value.
1—————
01 Not applicable. Do not change the default value.
1:00 — — — — —
02 Not applicable. Do not change the default value.
0—————
03 Not applicable. Do not change the default value.
15:00 — — — — —
2 Automatic setback function
00 Status: setback operation
1 (ON) 0/1 — — —
01 Setback operation start time
23:00 0:00~23:00 1:00 hour —
02 Setback operation stop time
5:00 0:00~23:00 1:00 hour —
3 Weather dependent set point
00 Low ambient temperature (Lo_A)
–10 –20~5 1 °C —
01 High ambient temperature (Hi_A)
15 10~20 1 °C —
02 Set point at low ambient temperature (Lo_Ti)
40 25~80 1 °C —
03 Set point at high ambient temperature (Hi_Ti)
25 25~80 1 °C —
4 Settings are not applicable
00 Not applicable. Do not change the default value.
1—————
01 Not applicable. Do not change the default value.
Fri — — — — —
02 Not applicable. Do not change the default value.
23:00 — — — — —
5 Automatic setback and disinfection set point
00 Not applicable. Do not change the default value.
70 — — — — —
01 Not applicable. Do not change the default value.
10 — — — — —
02 Leaving water setback temperature
50~101°C—
03 Room setback temperature
18 17~23 1 °C —
04 Not applicable. Do not change the default value.
1—————
6 Option setup
01 Optional room thermostat installed
00~2——
7 Option setup
00 Forced pump operation
1 (ON) 0/1 — —
8 Option setup
00 Remote controller temperature control
0 (OFF) 0/1 — —
01 Not applicable. Do not change the default value.
1—————
03 Not applicable. Do not change the default value.
1—————
04 Status: freeze-up prevention
0 0~2 1 —
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating)
0 –2~2 0.2 °C —
01 Leaving water thermistor auto corrective function
1 (ON) 0/1 1 —
02 Not applicable. Do not change the default value.
0—————
03 Leaving water temperature compensation value
(cooling)
0 –2~2 0.2 °C —
04 Not applicable. Do not change the default value.
0—————