Installation and operation manual
41
EWAQ016~064BAW + EWYQ016~064BAW
Packaged air-cooled water chiller
4PW70082-1E 2016.12
6.1.1. Field settings on the remote controller
First
code
Second
code
Setting name
Installer setting at variance
with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 User permission level
22~31
01 Room temperature compensation value
0 –5~5 0.5 °C 
02 Not applicable. Do not change the default value.
1—
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
1 (ON) 0/1
1 Settings are not applicable
00 Not applicable. Do not change the default value.
1—
01 Not applicable. Do not change the default value.
1:00
02 Not applicable. Do not change the default value.
0—
03 Not applicable. Do not change the default value.
15:00
2 Automatic setback function
00 Status: setback operation
1 (ON) 0/1
01 Setback operation start time
23:00 0:00~23:00 1:00 hour
02 Setback operation stop time
5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A)
–10 –20~5 1 °C
01 High ambient temperature (Hi_A)
15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti)
40 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti)
25 25~80 1 °C
4 Settings are not applicable
00 Not applicable. Do not change the default value.
1—
01 Not applicable. Do not change the default value.
Fri
02 Not applicable. Do not change the default value.
23:00
5 Automatic setback and disinfection set point
00 Not applicable. Do not change the default value.
70
01 Not applicable. Do not change the default value.
10
02 Leaving water setback temperature
50~101°C
03 Room setback temperature
18 17~23 1 °C
04 Not applicable. Do not change the default value.
1—
6 Option setup
01 Optional room thermostat installed
00~2
7 Option setup
00 Forced pump operation
1 (ON) 0/1 
8 Option setup
00 Remote controller temperature control
0 (OFF) 0/1 
01 Not applicable. Do not change the default value.
1—
03 Not applicable. Do not change the default value.
1—
04 Status: freeze-up prevention
0 0~2 1 
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating)
0 –2~2 0.2 °C
01 Leaving water thermistor auto corrective function
1 (ON) 0/1 1 
02 Not applicable. Do not change the default value.
0—
03 Leaving water temperature compensation value
(cooling)
0 –2~2 0.2 °C
04 Not applicable. Do not change the default value.
0—