D-EIMHP01812-24_00EN 11/47
OPERATION RANGE HEATING – EWYE-CZ
Figure 2 - Operating limits on EWYE-CZ in heating mode
OAT
Outside ambient temperature
CLWT
Condenser Leaving water temperature
Ref. 1
Unit operations in this area require OP. 192 HIGH AMBIENT TEMPERATURE KIT.
Ref. 2
Unit operations in this area require the enabling of the Brine version in the controller and the use of the
proper amount of glycol.
Ref. 3
Unit operations in this area require water delta T > 5 dK.
Ref. 4
Unit operations in this area require water delta T > 10 dK.
Ref. 5
Unit operations in this area require water delta T > 12 dK.
The charts shown above constitute a guideline on operating limits in the range.
Refer to the CSS selection software for the actual operating limits in the working conditions for each
model.
15
20
25
30
35
40
45
50
55
60
65
70
75
-30 -25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
LWT [
°C]
OAT [°C]
heating
Ref. 5
Ref. 4
Ref. 3