Daikin EWWS490VZXSA1 handleiding

67 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 20 van 67
D-EOMZC00106-17_07EN - 20/67
4.2.4 Condenser
This page contains basics settings for condensation control described in section 5.3.
Setpoint/Sub-Menu
Default
Range
Description
Cond LWT
-273.1°C
-
Present value of Condenser Leaving Water Temperature
Cond EWT
-273.1°C
-
Present value of Condenser Entering Water Temperature
Cond Target
25.0 °C
19.0…55.0 °C
Target for Condenser Leaving Water Temperature
Cond Fan Spd
0.0%
0.0…100.0%
Present value of Condenser Fan Speed
Tower Setpt 1
25.0 °C
19.0…55.0 °C
Setpoint for activation of Tower 1
Tower Setpt 1
27.0 °C
26.0…55.0 °C
Setpoint for activation of Tower 2
Tower Setpt 3
29.0 °C
28.0…55.0 °C
Setpoint for activation of Tower 3
Tower Setpt 4
31.0 °C
30.0…55.0 °C
Setpoint for activation of Tower 4
Tower Diff 1
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 2
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 3
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Tower Diff 4
1.5 °C
0.1…5.0 °C
Differential for deactivation of Tower 1
Min Vfd Sp
10.0%
0.0…49.0 %
Setpoint for minimum percentage of Vfd Speed
Max Vfs Sp
100.0%
55.0…100.0%
Setpoint for maximum percentage of Vfd Speed
PID Prop Gain
10.0
0.0…50.0
Proportional Gain of PID condensation controller
PID Der Time
1s
0...180s
Derivative Time of PID condensation controller
PID Int Time
600s
0…600s
Integral Time of PID condensation controller
Vfd Manual Speed
20.0%
0.0…100.0%
Setpoint for Vfd manual speed
4.2.5 Evaporator
This page contains basics settings for evaporator three way valve control (Optional).
Setpoint/Sub-Menu
Default
Range
Description
Cool Setp Offs
1.5°C
1.0…7.0°C
Offset on the cool setpoint to regulate the three way valve
Valve Type
NC to
Tower
NC to tower, NO to
Tower
Type of three way valve to tower
Min Valve Open
0.0%
0.0…60.0%
Valve minimum position
Max Valve Open
95.0%
50.0…100.0%
Valve maximum position
Kp
1
0.1…100
Proportional Gain of PID valve controller
Ti
2.0min
1.0…60.0min
Derivative Time of PID valve controller
Td
2.0min
1.0…60.0min
Integral Time of PID valve controller
4.2.6 Rapid Restart
This page shows if the function Rapid Restart is enabled by external contact and it allows to define the maximum black out
time in order to recover quickly the unit load.
Setpoint/Sub-Menu
Default
Range
Description
Rapid Restart=
Disable
Enable, Disable
Feature enable if Rapid Restart is installed
Pwr Off Time=
60s
-
Maximum black out time to enable Rapid Restart
4.2.7 Date/Time
This page will allow to adjust the time and date in the UC. This time and date will be used in the alarm log and to enable
and disable the Quiet Mode. Additionally its also possible to set the starting and ending date for the DayLight Saving time
(DLS) if used. Quiet Mode is a feature that is used to reduce the chiller noise. This is done by applying the maximum
setpoint reset to the cooling setpoint and increasing the condenser temperature target by an adjustable offset.
Setpoint/Sub-Menu
Default
Range
Description
VZ
Actual Time=
12:00:00
Set the time
Actual Date=
01/01/2014
Set the date
UTC Diff=
-60min
Difference with UTC
DLS Enable=
Yes
No, Yes
Enable DayLight Saving time
DLS Strt Month=
Mar
DayLight Saving time start month
DLS Strt Week=
2ndWeek
DayLight Saving time start week
DLS End Month=
Nov
NA, Jan…Dec
DayLight Saving time end month
DLS End Week=
1stWeek
1
st
…5
th
week
DayLight Saving time end week
Quiet Mode=
N/A
Disable, Enable
Activate Quiet Mode
QM Start Hr=
N/A
18…23h
Quiet Mode start hour
QM Start Min=
N/A
0…59min
Quiet Mode start minute
QM End Hr=
N/A
5…9h
Quiet Mode end hour
QM End Min=
N/A
0…59min
Quiet Mode end minute
QM Cond Offset=
N/A
0.0…14.0°C
Quiet Mode condenser target offset
On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure that the battery
is replaced regularly each 2 years (see section 3.6).