4 MENU STRUCTURE
All settings are divided in different menus. Each menu collects in a single page other sub-menus, settings or data related
to a specific function (for example Power Conservation or Setup) or entity (for example Unit or Circuit). In any of the
following pages, a grey box will indicate changeable values and the defaults.
4.1 Main Menu
Setpoint/Sub-
Menu
Default
Range
Description
Enter Password
-
Submenu to activate access levels
View/Set Unit
-
Submenu for unit data and settings
View/Set
Circuit
-
Submenu for circuit data and settings
Unit Status=
Off: Unit
Sw
Auto
Off: Ice Mode Tmr
Off: OAT Lockout (A/C
units only)
Off: All Cir Disabled
Off: Unit Alarm
Off: Keypad Disable
Off: Master Disable
Off: BAS Disable
Off: Unit Sw
Off: Test Mode
Off: Schedule Disable
Auto: Noise Reduction
Auto: Wait For Load
Auto: Evap Recirc (A/C
units only)
Auto: Water Recir (W/C
units only)
Auto: Wait For Flow
Auto: Pumpdn
Auto: Max Pulldn
Auto: Unit Cap Limit
Auto: Current Limit
Status of the Unit
Active
Setpoint=
7.0°C,
-
Water temperature active setpoint + link to Setpoint page
MS Ctrl Tmp=
-273.1°C,
-
Master slave controlled temperature + link to Master Slave
Data page
Evaporator
LWT=
-273.1°C,
-
Evaporator leaving water temperature + link to
Temperatures page
Condenser LWT=
-273.1°C,
-
Condenser leaving water temperature + link to
Temperatures page (W/C units only)
Unit Capacity=
0.0%,
-
Unit capacity + link to Capacity page
Unit Mode=
Cool,
-
Unit Mode + link to Available modes page
Unit Enable=
Enable,
-
Unit Enable state + link to unit and circuits enable page
Timers
-
Submenu for unit timers
Alarms
-
Submenu for alarms; same function as Bell Button
Commission
Unit
-
Submenu for commission unit
About Chiller
-
Application Info submenu
4.2 View/Set Unit
Setpoint/Sub-Menu
Default
Range
Description
Thermostat Ctrl
-
Submenu for Thermostatic control
Network Ctrl
-
Submenu for Network control
Vfd Settings
-
Submenu Vfd installation settings (A/C units only)
Pumps
-
Submenu for pump settings
Condenser
-
Submenu for Condenser tower control (W/C units Only)
Master/Slave
-
Submenu for Master Slave data and settings
Rapid Restart
-
Submenu for Rapid Restart Option
Date/Time
-
Submenu Date, Time and Quiet Night mode schedule
Scheduler
-
Submenu for Time Scheduler
Power Conservation
-
Submenu Unit Limiting functions
Electrical Data
-
Submenu for electrical data
Ctrl IP Setup
-
Submenu for controller IP-address setup
Daikin on Site
-
Submenu for connection to Daikin cloud DoS
Menu Password
-
Submenu Disable Password for User level