3.6 Controller maintenance
The UC requires to maintain the installed battery. Battery model is: BR2032 and it is produced
by many different vendors.
On board real time clock settings are maintained thanks to a battery mounted on the controller.
Make sure that the battery is replaced regularly each 2 years.
Battery is only used to supply the onboard real time clock. All the other settings are retained in a
non volatile memory.
To replace the battery gently remove the plastic cover of the controller display using a screw
driver as shown in the following pictures:
Be careful to avoid damages to the plastic cover. The new battery shall be placed in the proper
battery holder which is highlighted in the following picture, respecting the polarities indicated
into the holder itself.
3.7 Software Update procedure
UC can be updated by using an SD card and an appropriate pin.
Actual BSP and software version installed on UC can be checked in the About Chiller page.