Handleiding
Je bekijkt pagina 81 van 84

Air cooled inverter water chiller 
OPERATION 
MANUAL 
EWAD TZ B 160-700 
Air cooled inverter water chiller 
D-EOMAC00909-16EN 
Operation Manual 
81 
7  Options 
7.1  Total Heat Recovery (Optional) 
This chiller can handle a total heat recovery option. This feature will require an additional module 
and sensors to read the entering and leaving heat recovery water temperatures, command a heat 
recovery water pump.  
The  heat recovery is  enabled  through the  Q8  switch  installed on  the  unit  and  requires  to  adjust 
settings on the unit controller in order to make it work as needed. First of all the function needs to 
be enabled on the main controller in order to display all the settings related to this function. With 
reference to section 4.3.5 the heat recovery enable setpoint has to be chanded to Enable. 
Setpoint/Sub-Menu 
Default 
Range 
Description 
Apply Changes= 
No 
No, Yes 
C1 # Of Fans= 
6 
Number of fans available. 
Heat Recovery= 
Enable 
Disable, Enable 
When this is done the controller will need to be reset by applying the changes. 
After  the  reboot  all  the  heat  recovery  data  and  settings  will  be  displayed  on  the  HMI.  In  the  
View/Set Unit – Temperatures the heat recovery entering and leaving water temperatures will be 
then visible. 
HR LWT= 
-273.1°C 
Heat Recovery Leaving Water Temperature (displayed only if Heat Recovery set on) 
HR EWT= 
-273.1°C 
Heat Recovery Entering Water Temperature (displayed only if Heat Recovery set on) 
Additionally the Heat Recovery setpoint and differential will become visible and can be adjusted as 
needed: 
Setpoint/Sub-Menu 
Default 
Range 
Description 
HR EWT Stp 
40.0°C 
30.0…50.0°C 
Heat Recovery Entering Water Setpoint 
HR EWT Dif 
2.0°C 
1.0…10.0°C 
Heat Recovery Water Temperature differential 
7.2  Energy Meter including Current Limit (Optional) 
An energy meter can be optionally  installed on the unit. The energy meter is connected through 
Modbus to the unit controller, which can display all relevant electrical data such as: 
  Line to Line Voltage (per phase and average) 
  Line Current (per phase and average) 
  Active Power 
  Cos Phi 
  Active Energy 
More details are described in chapter 4.2.10. All these data can be also accessed from a BMS by 
connecting it to a communication module. See the communication module manual for  details on 
the device and parameter settings. 
Both  the  energy  meter  device  and  the  unit  controller  need  to  be  properly  set.  The  instructions 
below detail how to set the energy meter. Refer to the specific instructions of the energy meter for 
more detail on the operation of the device. 
Bekijk gratis de handleiding van Daikin EWAD620TZPLB, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Daikin | 
| Model | EWAD620TZPLB | 
| Categorie | Airco | 
| Taal | Nederlands | 
| Grootte | 11976 MB | 








