OPERATION 
MANUAL 
Operation Manual 
80 
EWAD TZ B 160-700 
Air cooled inverter water chiller 
D-EOMAC00909-16EN 
Symptom 
Cause 
Solution 
Circuit  is  stopped  if  the  discharge 
temperature  reach  the  high  limit 
value. 
Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
Cx EcoEXVDrvError 
String in the alarm log: 
 Cx OffEcoEXVDrvError 
String in the alarm snapshot 
Cx OffEcoEXVDrvError 
Hardware Error 
Contact your service organization to 
get the problem solved. 
6.1.7.23 EXV Motor Not Connected 
This alarm indicates an abnormal condition of the EXV Driver. 
Symptom 
Cause 
Solution 
Circuit status is Off. 
Circuit is immediately stopped. 
Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
Cx OffEXVMotor 
String in the alarm log: 
 Cx OffEXVMotor 
String in the alarm snapshot 
Cx OffEXVMotor 
Valve not connected. 
Referring to the wiring diagram check 
if the valve is correctly connected to 
the module. 
6.1.7.24 Economizer EXV Motor Not Connected 
This alarm indicates an abnormal condition of the Economizer EXV Driver. 
Symptom 
Cause 
Solution 
Circuit  is  stopped  if  the  discharge 
temperature  reach  the  high  limit 
value. 
Bell  icon  is  moving  on  controller’s 
display. 
String in the alarm list: 
Cx EcoEXVMotor 
String in the alarm log: 
 Cx EcoEXVMotor 
String in the alarm snapshot 
Cx EcoEXVMotor 
Valve not connected. 
Referring to the wiring diagram check 
if the valve is correctly connected to 
the module. 