Air cooled inverter water chiller
OPERATION
MANUAL
Operation Manual
48
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
The Keypad enable signal cannot be modified with the user password level. If it is set to Disable
contact your local maintenance to check if it can be changed to Enable.
The last enable signal is coming through the high level interface, that mean from a Building
Management System. From a BMS connected to the UC using a communication protocol the unit
can be disabled. To see if the enable signal is coming from a BMS in the View/Set Unit and then
Status/Settings check the Control Source, if it is set to Network than the Network En SP setpoint in
the same page will reflect the actual signal coming from the BMS. If the value is set to Disable then
the unit cannot start. In this case check with your BAS company how the chiller is operated.
The Unit Status will inform about the current unit status, possible status will be described in the
following table:
Overall Status
Status
Description
Off:
Ice Mode Tmr
This status can be shown only if the unit can work in Ice Mode. The unit is off
because the Ice setpoint has been satisfied. Unit will remain off until the Ice
Timer has expired.
OAT Lockout
The unit cannot run because the Oustide Air Temperature is below the limit
foreseen for the condenser temperature control system installed in this Unit. If
the Unit has to run anyway check with your local maintenance how to proceed.
All Cir Disabled
No circuit is available to run. All circuits can be disabled by their individual enable
switch or can be disabled by a component safety condition active or can be
disabled by keypad or can be all in alarms. Check the individual circuit status for
further details.
Unit Alarm
A unit alarm is active. Check the alarm list to see what is the active alarm
inhibiting the unit to start and check if the alarm can be cleared. Refer to the
Troubleshooting section before proceeding.
Keypad Disable
The Unit has been disabled by keypad. Check with your local maintenance if it
can be enabled.
Loc/Rem Switch
The Local/Remote enable switch is set to disable. Turn it to Local to enable the
unit to start its starting sequence.
BAS Disable
Unit is disabled by BAS/BMS system. Check with the BAS company how to start
the unit.
Master Disable
Unit is disabled by the Master Slave function
Scheduler Disabled
Unit is disabled by the time scheduler.
With the Q0 switch in this position the unit is disabled. Pump will
not start in normal operational condition. Compressor are kept
disabled independently from the status of the individual enable
switches.
With the Q0 switch in this position the unit is enabled. Pump will
start if all other enable signals are set to enable and at least one
compressor is available to run
With the Q0 switch in this position the unit can be enabled using
the additional connections available on the connection terminals.
A closed loop will identify an enable signal, this can come from a
remote switch or a timer by example.