Air cooled inverter water chiller
OPERATION
MANUAL
Operation Manual
18
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
push’n’roll the individual field will be highlighted to allow an easy introduction of the numeric
password. By changing all fields, the 4 digits password will be entered and, if correct, the additional
settings available with that password level will be disclosed.
E
n
t
e
r
P
a
s
s
w
o
r
d
2
/
2
E
n
t
e
r
P
W
5
*
*
*
The password will time out after 10 minutes and is cancelled if a new password is entered or the
control powers down. Entering an invalid password has the same effect as continuing without a
password.
Once a valid password has been entered, the controller allows further changes and access without
requiring the user to enter a password until either the password timer expires or a different
password is entered. The default value for this password timer is 10 minutes. It is changeable from
3 to 30 minutes via the Timer Settings menu in the Extended Menus.
3.4 Editing
The Editing Mode is entered by pressing the navigation wheel while the cursor is pointing to a line
containing an editable field. Once in the edit mode pressing the wheel again causes the editable
field to be highlighted. Turning the wheel clockwise while the editable field is highlighted causes
the value to be increased. Turning the wheel counter-clockwise while the editable field is
highlighted causes the value to be decreased. The faster the wheel is turned the faster the value is
increased or decreased. Pressing the wheel again cause the new value to be saved and the
keypad/display to leave the edit mode and return to the navigation mode.
A parameter with an “R” is read only; it is giving a value or description of a condition. An “R/W
indicates a read and/or write opportunity; a value can be read or changed (providing the proper
password has been entered).
Example 1: Check Status, for example -is the unit being controlled locally or by an external
network? We are looking for the Unit Control Source Since this a unit status parameter, start at
Main Menu and select View/Set Unit and press the wheel to jump to the next set of menus. There
will be an arrow at the right side of the box, indicating that a jump to the next level is required.
Press the wheel to execute the jump.
You will arrive at the Status/ Settings link. There is an arrow indicating that this line is a link to a
further menu. Press the wheel again to jump to the next menu, Unit Status/Settings.
Rotate the wheel to scroll down to Control Source and read the result.
Example 2: Change a Set point, the chilled water set point for example. This parameter is
designated as Cool LWT Set point 1 and is a unit set parameter. From the Main Menu select
View/Set Unit. The arrow indicated that this is link to a further menu.
Press the wheel and jump to the next menu View/Set Unit and use the wheel to scroll down to
Temperatures. This again has an arrow and is a link to a further menu. Press the wheel and jump