Air cooled inverter water chiller
OPERATION
MANUAL
Operation Manual
12
EWAD TZ B 160-700
Air cooled inverter water chiller
D-EOMAC00909-16EN
1.6.1.11 Demand limit
This optional function can be used to limit the unit capacity percentage to a changeable limit value.
This limitation cannot be directly linked to a corresponding limitation of the unit current (50%
demand limit can differ from 50% of the unit FLA).
The demand limit signal can be changed continuously between 4 and 20 mA. The Microtech III will
convert this signal into a unit capacity limitation changing between minimum capacity and full
capacity with a linear relationship. A signal between 0 and 4mA will correspond to a full unit
capacity, in this way if nothing is connected to this input no limitation will be applied. The maximum
limitation will never force a unit shutdown.
1.6.1.12 Setpoint override
This input allows to apply an offset on the Active Setpoint to adjust the operating point of the
ELWT. This input can be used to maximize the comfort.
1.6.1.13 Pump VFD Signal (optional)
When the inverter kit option is required, by default the speed control is customer supplied. The
“Pump VFD Signal” terminals allow the customer to connect an external speed reference wire to
the inverter. These terminals are placed inside the main electrical panel.