5 | Application guidelines
Installer reference guide
39
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W
Daikin Altherma 3 H HT W
4P587501-1A – 2020.01
INFORMATION
To increase comfort and performance, we recommend to install the valve kit option
EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
0 (Leaving water): Unit operation is
decided based on the leaving water
temperature.
Number of water temperature zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
5.2.3 Multiple rooms – TwoLWT zones
In this document:
Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
CAUTION
If there is more than one leaving water zone, ALWAYS install a mixing valve station in
the main zone to decrease (in heating)/increase (in cooling) the leaving water
temperature when the additional zone has demand.
Typical example:
Room (zone) Heat emitters: Design temperature
Living room (main zone) Underfloor heating:
In heating: 35°C
In cooling: 20°C (only refreshment, no
real cooling allowed)
Bed rooms (additional zone) Heatpump convectors:
In heating: 45°C
In cooling: 12°C