19 Commissioning
Installation and operation manual
38
ERA200~300AMYFB
Inverter outdoor unit for AHU option kit and air curtains
4P780153-1 – 2024.07
[1‑5] [1‑6]
Code Shows ...
[1‑5] The current T
e
target parameter position
[1‑6] The current T
c
target parameter position
[1‑10]
Shows the total number of connected indoor units.
[1‑17] [1‑18] [1‑19]
Code Shows ...
[1‑17] The latest malfunction code
[1‑18] The 2nd last malfunction code
[1‑19] The 3rd last malfunction code
[1‑40] [1‑41]
Code Shows ...
[1‑40] The current cooling comfort setting
[1‑41] The current heating comfort setting
18.1.7 Mode 2: field settings
[2‑8]
T
e
target temperature during cooling operation.
[2‑8] T
e
target [°C]
0 (default) Auto
2 6
3 7
4 8
5 9
6 10
7 11
[2‑9]
T
c
target temperature during heating operation.
[2‑9] T
c
target [°C]
0 (default) Auto
1 41
2 42
3 43
4 44
5 45
6 46
[2‑20]
Manual additional refrigerant charge.
[2‑20] Description
0 (default) Deactivated.
1 Activated.
To stop the manual additional refrigerant
charge operation (when the required additional
refrigerant amount is charged), push BS3. If
this function was not aborted by pushing BS3,
the unit will stop its operation after 30minutes.
If 30minutes was not sufficient to add the
needed refrigerant amount, the function can be
reactivated by changing the field setting again.
[2‑22]
Automatic low noise setting and level during night time.
By changing this setting, you activate the automatic low noise
operation function of the unit and define the level of operation.
Depending on the chosen level, the noise level will be lowered. The
start and stop moments for this function are defined under setting
[2‑26] and [2‑27]. For more details about settings [2‑26] and [2‑27],
see installer user reference guide
[2‑22] Description
0 (default) Deactivated
1 Level 1 Level 5<Level 4<Level
3<Level 2<Level 1
2 Level 2
3 Level 3
4 Level 4
5 Level 5
[2‑35]
Height difference setting.
[2‑35] Description
0 In case the outdoor unit is installed in the
lowest position (indoor units are installed on a
higher position than outdoor units) and the
height difference between the highest indoor
unit and the outdoor unit exceeds 40m, the
setting [2‑35] should be changed to 0.
1 (default)
[2‑60]
Supervisor remote controller setting. A power reset is required to
save this setting.
For details about the supervisor remote controller, see
"13.1.2 System layout requirements" [4 17] or refer to the remote
controller installation and user reference guide.
[2‑60] Description
0 (default) No supervisor remote controller connected to
the system
1 Supervisor remote controller connected to
system
18.1.8 Indoor unit field setting
15(25)-13
Safety system deactivation.
When the room where the indoor unit is installed is big enough that
no safety measure is required, the R32 leak safety system in that
indoor unit can be deactivated by this setting.
Safety system deactivation
Setting 1
st
code Function 2
nd
code Description
15/25 13 R32 leak safety
system setting
01 Disabled
02 Enabled
19 Commissioning
CAUTION
See "2 Specific installer safety instructions" [4 5] to make
sure commissioning complies with all safety regulations.
NOTICE
General commissioning checklist. Next to the
commissioning instructions in this chapter, a general
commissioning checklist is also available on the Daikin
Business Portal (authentication required).
The general commissioning checklist is complementary to
the instructions in this chapter and can be used as a
guideline and reporting template during commissioning and
hand-over to the user.