Daikin Home Controls
4P701747-1A – 2023.10
▪ The minimum capacity of the unit is typically higher than the heat load of 1
room. The consequence is less efficient unit operation (ON/OFF operation
because of minimum load condition).
▪ Due to the colder neighbouring rooms, a higher leaving water temperature
setpoint is needed to reach the desired room temperature. This has a negative
impact on the efficiency of the unit.
9.1.4 Technical specifications
Typical value of flow rate in 1 underfloor heating (UFH) loop: 1~2l/min
▪ Typical value of Delta T in 1 UFH loop: 3~8°C
▪ Typical load of 1 UFH loop: 4.18kJ/kgK×2l/min×1/60min/s×5°C=0.7kW
Sanity check based UFH load:
▪ Typical UFH output: 30~100W/m²
▪ Typical surface covered by 1 UFH loop: 10~20m²
▪ Typical load of 1 UFH loop: 65W/m²×15m²≈1kW
Typical minimum capacity of heat pump ≈ ± 3kW
(1)
▪ Continuous operation requires 3~4 open UFH loops
▪ 3 UFH loops open: spurious ON/OFF operation expected
▪ 2 UFH loops open: not very frequent ON/OFF operation expected
▪ 1 UFH loop open: frequent ON/OFF operation expected
Note: When the minimum volume and the minimum flow rate can be reached
with all valves closed, there is no need to add a bypass valve to the system.
To guarantee that the minimum load corresponds with the minimum capacity of
the unit, there are 2 options:
1 Keep a number of UFH loops uncontrolled (without valve actuators connected
to the DHC Floor Heating Controller). The uncontrolled loops are only heated
from the moment there is a heat demand from any of the controlled rooms. It
is recommended to take the room that is large enough and is used most
frequently.
2 The DHC Floor Heating Controller will always keep 2 heating zones active. Some
heating zones offer 2 electrical outputs. If the heating zones with dual output
are prioritised during allocation, the minimum capacity will be matched faster
during a heat demand. In this case, 2 active heating zones will correspond with
3~4 UFH loops.
9.2 About non-connected solutions
Another way to use the DHC accessories is without internet connection. This type
of configuration ONLY supports specific special applications, that make use of a
direct wireless connection between the accessories and are NOT using a DHC
Access Point. Without a DHC Access Point, these applications do NOT offer the
convenience of the ONECTA app for configuration or monitoring.
It is possible to move to a connected ONECTA based system at a later time, but this
will require the purchase of a DHC Access Point and a complete recommissioning.
(1)
This minimum capacity will be different for higher capacity units. A useful rule of thumb is that the minimum capacity is
roughly 30-40% of the published capacity table.