6 Configuration
Installation manual
23
EKMBPP1+EKMBPP1A
Modbus adapter
4P720139-1C – 2024.11
INFORMATION
The Modbus master timeout ONLY overrules the Recommended
on and Forced on Smart Grid operation in case no holding
register write command is received for 120 seconds. The
Forced off Smart Grid operation will NOT be overruled.
6.3.4 Terminating resistor settings
The EKMBPP1(A) has 3 slide switches to set the terminating
resistance. See "3.1 Components" [4 7] for the location of the slide
switches on the PCB.
Terminating resistor setting Resistance (Ω)
OFF
ON
SS1 SS2
SS3
0
OFF
ON
SS1 SS2
SS3
100
OFF
ON
SS1 SS2
SS3
120
6.4 Control functions
6.4.1 Unit control
Holding registers allow the EKMBPP1(A) to control the functions of Sky
Air and VRV air conditioning units that are available from the standard
remote controller.
For more information about the types of registers and possible data
types, see "6.3.2 Modbus registers" [4 21]. The following holding
registers are available:
Holding register Address Name Range
(a)
Description
H0001 40002 Setpoint 16~32 -
H0002 40003 Fan speed
(b)
1~5
(c)
▪
1: Low
▪
2: Medium Low
(d)
▪
3: Medium
▪
4: Medium High
(d)
▪
5: High
(e)