6 Configuration
Installation manual
22
EKMBPP1+EKMBPP1A
Modbus adapter
4P720139-1C – 2024.11
INFORMATION
Throughout this document, when reference is made to any
registers, the notation of registers and their addresses follows
a consistent format:
▪ H0010 where H indicates a holding register, and 0010
refers to the register address.
▪ I0010 where I indicates an input register, and 0010 refers
to the register address.
6.3.3 Modbus master timeout
The EKMBPP1(A) can be configured to operate with an optional
Modbus master timeout. When no holding register occurs for a period of
120 seconds, a timeout event occurs: all units switch on with their
current settings and the status LEDs indicate an RS-485
communication timeout. For more information about LED behaviour,
see "6.1 Status LEDs" [4 18].
DIP switch setting Timeout configuration
ON
1 2 3 4 5 6 7 8 9 10
No Modbus master timeout
ON
1 2 3 4 5 6 7 8 9 10
No Modbus master timeout
ON
1 2 3 4 5 6 7 8 9 10
Modbus master timeout in case no holding register
write command occurs for 120seconds.
▪
All units switch on with the current settings.
▪
Remote controllers are unlocked.
▪
The value of the Global Update register is set to
OnChange.
ON
1 2 3 4 5 6 7 8 9 10
Modbus master timeout in case no holding register
write command occurs for 120seconds.
▪
All units switch on with the current settings.
▪
The lock state of the remote controllers remains
unchanged. However, remote controller ON/OFF
operation is unlocked. If it is switched OFF after
this, the remote controller ON/OFF operation is
locked again.