5 Installation
Installation manual
17
EKMBPP1+EKMBPP1A
Modbus adapter
4P720139-1C – 2024.11
INFORMATION
The EKMBPP1(A) can operate in Master or Slave mode
with any remote controller. Note that some wireless remote
controllers (BRC*) may require the corresponding receiver
to be configured to operate in Sub (S) mode when the
EKMBPP1(A) is in Main (M) mode. See the installation
manual of the unit for more information.
Only 1 Modbus master is allowed.
INFORMATION
Only valid for EKMBPP1A: No more than 32 Modbus devices
including the Modbus Master must be installed on a single
network bus. Additional devices can be added by using the
RS-485 physical layer repeater.
Only valid for EKMBPP1: No more than 7 EKMBPP1 devices
must be installed on a single network bus.
5.4.4 To connect the RS-485 wiring
The RS-485 D-Bus MUST be installed using a twisted pair cable, as
shown in the following figure, to connect terminals DA(+) and DB(-).
Terminal DA(+) MUST be connected to all other DA(+) terminals, on
every EKMBPP1(A) kit.
Terminal DB(-) MUST be connected to all other DB(-) terminals, on
every EKMBPP1(A) kit.
The common terminal ground (GND) MUST be connected together,
on every EKMBPP1(A) kit. When using a shielded cable, the shield
can be used for this purpose.