Daikin EKMBDXB7V1 handleiding

56 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 8 van 56
4P642495-1 2020.10 Page 7 of 52
1.3.5 Push buttons
BS1 till BS5 have no meaning
1.3.6 Dipswitch meaning
Attention: Dipswitch on/off status is detected during power on of the PCB only. A power reset is needed after
setting the switches.
Dipswitch DS1 & DS2 setting:
RS485 Modbus communication speed
DS1 pin 2:Off
DS1 pin 2:On
9600 bps
19200 bps
Modbus communication parity / stop bit
DS1 pin 3:Off 4:Off
DS1 pin 3:Off 4: On
DS1 pin 3:On 4:Off
DS1 pin 3:On 4:On
Even 1 stop bit
Odd 1 stop bit
None 2 stop bit
None 1 stop bit
Modbus address setting
DS2 pin 1/2/3/4
When Modbus address is set (eg 1..15), then modbus RS485 communication is
enabled.
Off/Off/Off/Off
No Modbus address is set, meaning no modbus RS485 communication
Off/Off/Off/On
Off/Off/On/Off
On/On/On/On
Address 1
Address 2
Address 15
Attention:
During software upload with updater PC program via RS485 port a specific dipswitch setting is required.
Refer to chapter 4.2.3 Method 2) Update with a USB/RS485 converter.” for details.
Remark: DS1 pin 1: not used.

Bekijk gratis de handleiding van Daikin EKMBDXB7V1, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkDaikin
ModelEKMBDXB7V1
CategorieNiet gecategoriseerd
TaalNederlands
Grootte7895 MB