4P642495-1– 2020.10 Page 7 of 52
1.3.5 Push buttons
BS1 till BS5 have no meaning
1.3.6 Dipswitch meaning
Attention: Dipswitch on/off status is detected during power on of the PCB only. A power reset is needed after
setting the switches.
Dipswitch DS1 & DS2 setting:
RS485 Modbus communication speed
DS1 pin 2:Off
DS1 pin 2:On
9600 bps
19200 bps
Modbus communication parity / stop bit
DS1 pin 3:Off 4:Off
DS1 pin 3:Off 4: On
DS1 pin 3:On 4:Off
DS1 pin 3:On 4:On
Even 1 stop bit
Odd 1 stop bit
None 2 stop bit
None 1 stop bit
Modbus address setting
DS2 pin 1/2/3/4
When Modbus address is set (eg 1..15), then modbus RS485 communication is
enabled.
Off/Off/Off/Off
No Modbus address is set, meaning no modbus RS485 communication
Off/Off/Off/On
Off/Off/On/Off
…
On/On/On/On
Address 1
Address 2
Address 15
Attention:
During software upload with updater PC program via RS485 port a specific dipswitch setting is required.
Refer to chapter “4.2.3 Method 2) Update with a USB/RS485 converter.” for details.
Remark: DS1 – pin 1: not used.