16 Configuration
Installation and operation manual
29
EKEACBVE + EKEXVA50~500
Option kit for combination of Daikin outdoor units with field-
supplied air handling units
4P724517-1 – 2023.06
16.2 Field settings
Setting Value (bold = default
setting)
10(20)–2
Control temperature selection for room
air thermistor
1 Use both the unit
sensor (or remote
sensor if installed)
and the remote
controller sensor.
2 Use the suction air
sensor only (or the
remote sensor if
installed).
3 Use remote controller
sensor only.
10(20)–13
Target superheat for X, Y and W control
1 5°C
2 10°C
3 15°C
10(20)–14
Target subcool for X, Y and W control
1 3°C
2 5°C
3 10°C
10(20)–15
Operation mode restriction
(a)
1 Cooling and heating
2 Cooling only
3 Heating only
11(21)–9
Target evaporating temperature (T
e
S)
correction for W control
1 0°C
2 –1°C
3 –2°C
4 +1°C
11(21)–10
Target condensing temperature (T
c
S)
correction for W control
1 0°C
2 +1°C
3 +2°C
4 –1°C
11(21)–11
Expansion valve kit capacity class
(a)
1 0
2 50
3 63
4 80
5 100
6 125
7 140
8 200
9 250
10 300
11 350
12 400
13 450
14 500
11(21)–12
Setpoint selection for Z control
(b)
1 Remote controller
2 C1C2 input
11(21)–13
Cooling/heating selection method
(a)
To change this setting, see "16.1To
configure the control box"[427].
1 Remote controller
2 T3T4 input
11(21)–14
Use of the centralised controller
(a)
1 Enabled
2 Disabled
12(22)–1
External operation ON/OFF input (T1T2
input)
1 Forced OFF
2 Operation ON/OFF
3 Protective device
Setting Value (bold = default
setting)
12(22)–2
Thermostat differential changeover (if
remote sensor is used)
1 1°C
2 0.5°C
12(22)–3
Fan operation at thermostat off (heating)
1 ON
2 ON
3 OFF
12(22)–6
Fan operation at thermostat off (cooling)
1 ON
2 ON
3 OFF
12(22)–11
Hot start maximum duration time
1 0 minutes
2 3 minutes
3 5 minutes
4 10 minutes
13(23)–2
Fan operation during defrost and oil
return
1 OFF
2 ON
13(23)–13
Temperature control type
(a)
1 X control
2 Y control
3 W control
4 Z control
5 Z' control
13(23)–14
Target evaporating temperature for Y
control (cooling)
(c)
1 5°C
2 6°C
3 7°C
4 8°C
5 9°C
6 10°C
7 11°C
8 12°C
13(23)–15
Target condensing temperature for Y
control (heating)
(d)
1 43°C
2 44°C
3 45°C
4 46°C
5 47°C
6 48°C
7 49°C
14(24)–2
Discharge air temperature correction
factor
1 0°C
2 0.5°C
3 1°C
4 1.5°C
5 2°C
6 2.5°C
7 3°C
8 3.5°C
9 4°C
10 4.5°C
11 5°C
12 5.5°C
13 6°C
14 6.5°C
15 7°C
14(24)–3
Master-slave function
(e)
1 Not active
2 Master
3 Slave