12 Special requirements for R32 units
Installation and operation manual
18
EKEACBVE + EKEXVA50~500
Option kit for combination of Daikin outdoor units with field-
supplied air handling units
4P724517-1 – 2023.06
English Translation / description
Zone 2: Actions required Zone 2: Actions required
(IEC60335-2-40:2022 Annex
GG.9.2)
"Figure 3"[44]:
English Translation / description
260LFL Absolute maximum for the total
refrigerant charge in the system
50%LFL×H×(A
tot
or A
inst
)
(valid for m
c
>1.84 kg)
Maximum refrigerant charge to
prevent mechanical extraction
50%LFL×H×(A
tot
or A
inst
)
(valid for m
c
>1.84kg)
A
inst
Installation space area
A
min
Minimum A
tot
or A
inst
(based on
total refrigerant charge) to
prevent mechanical extraction
A
tot
Total conditioned space area
A
tot
is the sum of the floor areas
of all the spaces connected by
ducts to the air handling unit.
Spaces where the airflow can be
limited by zoning dampers, must
NOT be included in the
determination of A
tot
.
H Height of the room = 2.2m
LFL Lower flammability limit =
0.307kg/m³ for R32
m
c
Total refrigerant charge in the
system
3a: Requirements for AHU
installation location
(only applicable for indoor
installations)
3a: Requirements for air handling
unit installation location
(only applicable for indoor
installations)
Zone 1: No action required Zone 1: No action required
Zone 2: Additional ventilation in
the installation location required
Zone 2: Additional ventilation in
the installation location required
Zone 3: Out of scope standard Zone 3: Out of scope standard
(IEC60335-2-40:2022)
3b: Requirements for spaces
served by AHU
3b: Requirements for spaces
served by air handling unit
Zone 1: Only circulation airflow
required
Zone 1: Only circulation airflow
required
Zone 2: Circulation airflow +
Mechanical extraction
Zone 2: Circulation airflow +
Mechanical extraction
Zone 3: Out of scope standard Zone 3: Out of scope standard
(IEC60335-2-40:2022)
12.1 Conditioned space requirements
If the system uses R32 refrigerant, extra safety measures might be
required because R32 refrigerant is mildly flammable. This means
that the system is restricted with respect to the total refrigerant
charge and/or the floor area served.
12.2 Determination of the safety
requirements
Once the total refrigerant in the system has been determined, use
the flowchart below to establish the R32 safety requirements:
m
c
≤ 16 kg ?
▪ No need to install supply and
return air isolation dampers on the
air handling unit.
▪ No need to check the minimum
supply airflow rate of the air
handling unit.
No
No
Yes
No R32 safety measures required
Input: Total refrigerant charge in the system (m
c
)
(see chapter "11.7 Air handling unit")
▪ Install supply and return air
isolation dampers on the air
handling unit.
▪ Check the minimum supply airflow
rate of the air handling unit.
R32 safety measures required
Smallest room area ≥ A
min_room
?
(see figure 1 at the beginning of this manual)
Yes
Note: In case the air handling unit is installed indoors, see figure 3a
to determine if additional ventilation in the installation space is
required.
12.2.1 Example 1
Installation of 6 HP R32 system:
▪ Total conditioned space area: 100m²
▪ Smallest room area: 35m²
▪ Release height (h
0
): 2.2m
▪ Total refrigerant charge: 6.6kg
▪ Outdoor installation of air handling unit
0
2
4
6
8
10
12
14
16
m
c
[kg]
0 40 80 100 120
[m
2
]
16020 60 140
h
0
=1.8 m
h
0
=2.2 m
h
0
=2.5 m
1: Requirements for spaces served by AHU (m
c
≤16 kg)
Measures must be provided
following figures 2 and 3
No R32 safety requirements
35=A
room
27.6=A
min_room
6.6
Based on figure 1, no R32 safety measures are required
(A
room
>A
min_room
).
12.2.2 Example 2
Installation of 8 HP R32 system:
▪ Total conditioned space area: 140m²
▪ Smallest room area: 50m²
▪ Release height (h
0
): 2.2m
▪ Total refrigerant charge: 14.4kg
▪ Outdoor installation of air handling unit
Based on the smallest room area, "Figure 1"[42] indicates to follow
the requirements in figures 2 and 3.