<About R32 Alarm function>
■
I cannot nd the management point for which an R32 Alarm Stop was executed
• Check the list screen, because it displays the status of the management points.
■
I want to know the On/Off timing of the R32 Alarm buzzer and lamp
• See the following table for the On/Off timing.
Alarm and lamp On/Off timing
On
• When one of the indoor unit management points detects R32 refrigerant leakage.
• When R32 refrigerant leakage is detected again after the alarm and lamp are turned
off.
Off
When all indoor unit management points in which R32 refrigerant leakage occurred
enter one of the following states.
• The R32 alarms are stopped from the central monitoring screen.
• The R32 refrigerant leakages that occurred in the units are cleared.
• Communication error
• During maintenance
■
The buzzer/lamp goes on even when R32 refrigerant leakage is not occurring.
• Make sure that you do not use any ExternalDio management points allocated for the alarm
and lamp together with the auto control functions such as the schedule control and demand
control. Otherwise, an unintended behaviour may occur.