User’s Manual EM11A015H
intelligent Touch Manager
321
<When the device is a ventilator>
If the demand control is cancelled after communication is recovered, the device restarts
automatically when the demand control is cancelled.
If communication is recovered after the demand control is cancelled, the device restarts
automatically when communication is recovered.
<When the device is a D3Dio, External Dio or BACnet Dio>
If the demand control is cancelled after communication is recovered, the device remains stopped
even when the demand control is cancelled.
If communication is recovered after the demand control is cancelled, the device restarts
automatically when communication is recovered.
■
If both the demand control and schedule control are enabled for the same management point,
which one takes priority?
• If both the demand and schedule control functions execute the outdoor unit capacity control for
the same management point, the priority is given to a control with tighter restriction.
Example)
Demand Capacity control: 70%
Schedule Capacity control: 40%
In this case, the capacity control: 40% will be used.