User’s Manual EM11A015H
intelligent Touch Manager
315
Starting/stopping air conditioners is not possible from the Standard View screen.
Check the monitoring screen for the “Central controlled” sign, as shown in the gure below.
When “Central controlled” is displayed, the iTM only performs monitoring if it is instructed by a
higher-level central device (Interface for use in BACnet etc.) to put priority on it by stopping the
central control of lower-level equipment.
<Regarding the operation of Chiller management points>
Cautions when monitoring/setting up a Chiller
A Chiller management point can read and write the specific objects on a MicroTech III
controller (POL687.70/MCQ) which is embedded in a Chiller via BACnet/IP connection.
On that basis, the total operation of a Chiller unit (or a Chiller plant interlocking pumps and
others) from intelligent Touch Manager should be ensured by mechanical the installers and
control engineering rms.
The Warning Alarm for Chiller management points does not display any error.
The Warning Alarm for Chiller management points does not display any error. However, you
can check the Detailed Information screen for error codes.