User’s Manual EM11A015H
intelligent Touch Manager
314
■
An indoor unit cannot be started using remote controller.
• Remote controller may be disabled.
An indoor unit may not be started/stopped, or its operation mode, set temperature changed
depending on the remote controller operation settings.
Check remote controller operation settings from the Standard View screen (List View) or R/C
Prohibition tab of the Detailed Setup screen.
For details of remote controller operation settings, see “2-6 Enabling/Disabling Remote
Controller”.
■
Operation of room air conditioners is no longer possible.
• If “Operation Mode” in “R/C Prohibition” is set to “Prohibited”, “Start/Stop” and “Setpoint” will be
set to “Prohibited” even if you set “Start/Stop” to “Permitted”.
■
An area or indoor unit cannot be operated from the Standard View screen.
• Check the Standard View screen for the “Emergency Stop” icon, as shown in the gure below.
If an emergency stop order is received, all air conditioners connected to the iTM will stop by
default. Furthermore, operating air conditioners from a central control device or remote
controller is impossible while an emergency stop order is present.
The “Emergency Stop” icon will disappear and operation from the iTM will become possible
when the emergency stop order stops.