7 | Smart Grid application
Installer reference guide
43
BRP069A61+BRP069A62
Daikin Altherma LAN adapter
4P464229-1E – 2023.11
INFORMATION
▪ The system will ONLY buffer energy when the indoor unit is not in normal
operation. Normal operation has priority over energy buffering. Normal operation
can be any of the following:
▪ Normal operation can be any of the following: Space heating/cooling
(setpoint is not reached), Domestic hot water operation (setpoint is not
reached during a scheduled operation or a reheat operation), or safety functions
(e.g. Antifrost or Disinfection).
▪ On the configuration web interface, the buffering is default set to "domestic hot
water tank only".
▪ The maximum temperature during domestic hot water tank buffering is the
maximum tank temperature for the applicable tank type.
▪ The space heating/cooling setpoint during room buffering is the comfort setpoint
for the room. Units that cannot set these values via the user interface take 21°C
(for heating) and 24°C (for cooling) as default values.
▪ The system will ONLY buffer energy during space heating if the space heating
setpoint is lower than the heating comfort setpoint. The system will ONLY buffer
energy during space cooling if the space cooling setpoint is higher than the
cooling comfort setpoint.
7.1.2 Power limitation
In the "Recommended ON" operation mode, the power consumption of the heat
pump system is limited either statically or dynamically. In both cases, it is possible
to include the power consumption of the electrical heaters in the calculation
(default NOT the case).
IF THEN
Static power limitation
(Static power limitation)
The power consumption of the indoor
unit is limited statically based on a fixed
value (default 1.5kW) that is set in the
configuration web interface. During
energy buffering, the power
consumption of the indoor unit will NOT
exceed this limit.
The value for this setting is only used if
the system does not include an
electricity meter (on the configuration
web interface: Pulse meter setting: "No
meter"). Otherwise, make use of
dynamic power limitation.
Dynamic power limitation
(Pulse meter setting)
The power limitation is auto-adaptive,
and dynamically performed based on
the power injection into the grid,
measured by the electricity meter. To
minimise the power injection into the
grid, the indoor unit operates as much
as possible.